Ordering Information
Reflective Memory Xchange Module for RX3i
VMICBL-000-F5-0xx,
where 0xx distinguishes different lengths
Installation in Hazardous Locations
EQUIPMENT LABELED WITH REFERENCE TO CLASS I, GROUPS A, B, C & D, DIV. 2
HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, D
OR NON-HAZARDOUS LOCATIONS ONLY
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2;
WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER
BEFORE REPLACING OR WIRING MODULES; AND
WARNING - EXPLOSION HAZARD - DO NOT CONNECT OR DISCONNECT EQUIPMENT
UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE
NONHAZARDOUS.
EMC Installation Requirements
To meet EN 55011 and FCC Class A radiated emissions, the Control system in which the
IC695RMX128 module is used shall be mounted in a metal enclosure. All surfaces of the enclosure
must be adequately grounded to adjacent surfaces to provide electrical conductivity. Wiring external
to the enclosure must be routed in metal conduit or the equivalent. The conduit must be mounted to
the enclosure using standard procedures and hardware to ensure electrical conductivity between the
enclosure and conduit.
Applications using this module outside a grounded metal enclosure may experience RF interference
at 956.24MHz, 3.08GHz, or 3.29GHz.
When installing, operating, or maintaining the IC695RMX128, personnel must insure any electrostatic
charge is discharged through the use of a grounded ESD strap or other means.