214 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Appendix
8
Menu Default Setting Setting Options / Display
Heater ON/OFF Delay time for heater ON
0:30 min
Delay time for heater
to turn on
Heater ON/OFF Water temperature for heater ON
-4 °C
Setting of water
temperature to turn
on from water set
temperature�
Heater ON/OFF Water temperature for heater OFF
-2 °C
Setting of water
temperature to turn
off from water set
temperature�
6.2
*
1,
*
2
Cool
To set various water & ambient
temperatures for cooling�
Water temperatures for cooling ON
and
T for cooling ON�
Water temp. for cooling ON
Compensation curve
Cooling ON
temperatures in
compensation curve
or direct input�
Water temp. for cooling ON Compensation curve
X axis: 20 °C, 30 °C
Y axis: 15 °C, 10 °C
Input the 4
temperature points
(2 on horizontal X
axis, 2 on vertical Y
axis)
•If 2 zone system is selected, the 4 temperature points must also be input for Zone
2�
•“Zone 1” and “Zone 2” will not appear on the display if only 1 zone system�
*
1
The system is locked to operate without COOL mode� It can be unlocked only by authorised installers or our authorised service partners�
*
2
Only displayed when COOL mode is unlocked (This means when COOL mode is available)�