120 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Bi-bloc systems with hydrokit
Models Power supply 1 Power supply 2
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
WH-SDC0305J3E5 +
WH-UD03JE5
1 12.0 2.59 3 x 1.5 1 13.0 3.0 3 x 1.5
WH-SDC0305J3E5 +
WH-UD05JE5
1 12.0 2.59 3 x 1.5 1 13.0 3.0 3 x 1.5
WH-SDC0709J3E5 +
WH-UD07JE5
1 15.9 3.47 3 x 2.5 1 13.0 3.0 3 x 1.5
WH-SDC0709J3E5 +
WH-UD09JE5-1
1 15.9 3.47 3 x 2.5 1 13.0 3.0 3 x 1.5
WH-SDC12H6E5 +
WH-UD12HE5
1 24.0 5.30 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-SDC16H6E5 +
WH-UD16HE5
1 26.0 5.74 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-SXC09H3E5 +
WH-UX09HE5
1 29.0 6.27 3 x 4.0 1 13.0 3.0 3 x 4.0
WH-SXC12H6E5 +
WH-UX12HE5
1 29.0 6.27 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-SHF09F3E5 +
WH-UH09FE5
1 28.5 6.09
3 x 4.0 or
3 x 6.0
1 13.0 3.0 3 x 4.0
WH-SHF12F6E5 +
WH-UH12FE5
1 29.0 6.20
3 x 4.0 or
3 x 6.0
1 26.0 6.0 3 x 4.0
RCCB and power supplies Indoor unit / outdoor unit connection
RCCB
Power supplies
L N
L N
L
1
N
1
L
1
N
1
Power supply 1 Power supply 2
2
3
Terminal block
Indoor unit / outdoor unit
Connection of indoor unit
and outdoor unit
1 2 3
1 2 3
1
2
Terminals on indoor unit
Terminals on outdoor unit
Terminals on disconnector of the power supply
1
2
3
Models Power supply 1 Power supply 2
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
WH-SDC09H3E8 +
WH-UD09HE8
3 13.1 8.85 5 x 1.5 1 13.0 3.0 3 x 1.5
WH-SXC09H3E8 +
WH-UX09HE8
3 14.7 9.85 5 x 1.5 1 13.0 3.0 3 x 1.5
WH-SQC09H3E8 +
WH-UQ09HE8
3 14.7 9.85 5 x 1.5 1 13.0 3.0 3 x 1.5
WH-SHF09F3E8 +
WH-UH09FE8
3 14.5 9.67 5 x 1.5 1 13.0 3.0 3 x 1.5