Model Cooling capacities are based on
conditions below.
CS-
A34BB4P
Cooling
capacity
10.0 kW
3 phase, 50Hz, 400V / Indoor
temperature 27°C D.B. 19°C W.B. /
Outdoor temperature 35°C D.B. /
Standard air volume 27m
3
/min
Entering Temperature Air Entering
Condenser (°C D.B.)
Air 25 30 35 40 43
Temperature TC TC TC TC TC
D.B. W.B. kW kW kW kW kW
17 10.2 9.8 9.22 8.57 8.11
27 19 11.0 10.6 10.0 9.30 8.80
22 12.0 11.6 11.0 9.42 9.75
Entering Temperature Air Entering
Condenser (°C D.B.)
Air 25 30 35 40 43
Temperature IPT IPT IPT IPT IPT
D.B. W.B. kW kW kW kW kW
17 2.63 2.84 3.09 3.35 3.52
27 19 2.77 3.03 3.30 3.53 3.63
22 2.83 3.09 3.37 3.53 3.74
92