EasyManua.ls Logo

Panasonic CS-A24BD3P

Panasonic CS-A24BD3P
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. The main power is turned on while the transmission wires
between the indoor unit(s) are not connected (open circuit at
section A) / Symptom: / Nothing abnormal appears on the remote
control display. If operation is then started in this condition, the
combination of the 160C outdoor unit and the 40U indoor unit
(master unit) will cause abnormal operation to occur. / / If
operation continues, an abnormality will occur on the
refrigeration cycle and operation will stop.
- Remote control . . . CHECK flashes
- Indoor unit (master) . . . The LEDs on the printed circuit board
flash and operation stops
- Indoor unit (slave) . . . LED1 on the printed circuit board
illuminates and the unit does not operate at all
- Outdoor unit . . . The LEDs on the printed circuit board flash
and operation stops /
2. The main power is turned on while the power supply wires
between the indoor unit(s) are not connected (open circuit at
section B) / Symptom: / Same as above. If operation continues,
an abnormality will occur on the refrigeration cycle and operation
will stop. /
- Remote control . . . CHECK flashes
- Indoor unit (master) . . . The LEDs on the printed circuit board
flash
- Indoor unit (slave) . . . The LEDs on the printed circuit board
do not illuminate and the unit does not operate at all
- Outdoor unit . . . The LEDs on the printed circuit board flash
and operation stops /
3. The main power is turned on while the remote control connection

Related product manuals