8.1.2.3.3. The frequency change method
1. When (suction-setup) remains in a domain for 30 seconds, after shifting to relative control, a tap is adjusted according to the
domain and frequency changes relatively to the present condition.
2. A suction-setup is to other domains by load sudden change (remote control setting, open air introduction, etc.). When it moves,
an addition-and-subtraction tap is changed from the time of the following renewal of data.
8.1.3. Cooling Operation
8.1.3.1. Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.