Refer to the following table for the tightening torques. Be
sure to use two spanners to tighten.
(If the nuts are overtightened, it may cause the flares to
break or leak.)
3. After piping connection has been completed, make sure
that the joint areas of the indoor and outdoor units are
free from gas leakage by the use of nitrogen, etc.
4. Air purge within connection piping shall be carried out by
evacuation.
5. Close the tube joining area with putty heat insulator (local
supply) without any gap as shown in right figure. (To
prevent insects or small animal entering.)
6. The cardboard must be removed before installation of
piping work.
10.2.9. Heat Insulation
Charging With Refrigerant
At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30m. If the
equivalent pipe length used will be 30m or less, no additional charging will be necessary.
If the equivalent pipe length will be between 30 and 50m, charge with additional refrigerant according to the equivalent length
given in the table below.
- For standard type
Pump down operation
Operate the pump down according to the following procedures.
Flare nut fastening torque N•m {kgf•cm}
ø6.35mm 18 (180) ø15.88mm 65 (660)
ø9.52mm 42 (430) ø19.05mm 100 (1020)
ø12.7mm 55 (560)
Use a material with good heat-resistant
properties as the heat insulation for the pipes.
Be sure to insulate both the gas-side and
liquid-side pipes. If the pipes are not
adequately insulated, condensation or water
leakages may occur.
Liquid-side pipes Material that can
withstand 120°C or
higher
Gas-side pipes
Additional charging amount Equivalent length Minimum length
0.05kg/m 50m 7.5m
Procedure Notes
1. Confirm the valve on the liquid side and the gas side is surely open.
2. Press the PUMP DOWN switch on outdoor printed board for 1
second or more.
Perform the cooling operation for five minutes or more.
3. Shut the valve on the liquid side surely. When the valve is shut halfway, the compressor is occasionally
damaged.

Other manuals for Panasonic CS-F18DB4E5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-F18DB4E5 and is the answer not in the manual?

Panasonic CS-F18DB4E5 Specifications

General IconGeneral
BrandPanasonic
ModelCS-F18DB4E5
CategoryAir Conditioner
LanguageEnglish

Related product manuals