14.2. Sensible Capacity Chart
14.2.1.
●
CS-W7DKE
230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 2.28 1.73 0.65 2.13 1.66 0.70 1.98 1.59 0.75 1.80 1.51 0.81
19.0°C 2.30 0.71
19.5°C 2.50 1.81 0.66 2.34 1.74 0.71 2.18 1.67 0.76 1.98 1.59 0.82
22.0°C 2.73 1.88 0.67 2.55 1.81 0.73 2.37 1.74 0.78 2.16 1.66 0.84
14.2.2.
●
CS-W9DKE
230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 2.73 2.07 0.78 2.55 1.98 0.84 2.37 1.91 0.90 2.16 1.81 0.97
19.0°C 2.75 0.85
19.5°C 2.99 2.17 0.79 2.80 2.08 0.85 2.60 2.00 0.91 2.37 1.91 0.98
22.0°C 3.26 2.25 0.81 3.05 2.16 0.87 2.84 2.08 0.93 2.58 1.99 1.00
14.2.3.
●
CS-W12DKE
230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 3.57 2.71 1.03 3.34 2.60 1.10 3.10 2.49 1.18 2.82 2.37 1.27
19.0°C 3.60 1.12
19.5°C 3.92 2.83 1.04 3.66 2.72 1.12 3.41 2.62 1.20 3.10 2.50 1.30
22.0°C 4.27 2.94 1.06 3.99 2.83 1.14 3.72 2.73 1.22 3.38 2.60 1.32
TC - Total Cooling Capacity (kW) Indoor 27°C/19°C
SHC - Sensible Heat Capacity (kW) Outdoor 35°C/24°C
IP - Input Power (kW)
73
CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE