Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
Normal Deicing
Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice
operation. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (TRS CLOSE) or less for
50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and
after compressor starts for 1 minutes, deicing starts.
Deicing ends when
1. 12 minutes after deicing operation starts;
2. TRS senses the outdoor piping temperature rises to 4°C (TRS OPEN).
3. Deicing will not end immediately as time delay (Td) is valid as shown below.
Once deicing operation starts, it will not end for 60 seconds.
After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
26
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5
Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oy
www.ilmalämpöpumput.com

Other manuals for Panasonic CS-W9CKP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-W9CKP and is the answer not in the manual?

Panasonic CS-W9CKP Specifications

General IconGeneral
BrandPanasonic
ModelCS-W9CKP
CategoryAir Conditioner
LanguageEnglish

Related product manuals