remote control unit. Note that individual operation is not possible. 
20.1.1. Twin and triple operation setting
- The master unit and slave units are set automatically when the 
power is turned on. At this time, the indoor unit which is 
connected to the remote control unit becomes the master unit. / (If 
automatic setting is not possible, carry out the settings manually.)
- No distinction is made between master unit and slave units (slave 
unit 1 and slave unit 2) at the indoor unit or remote control.
- Install the remote control to the master unit. (It cannot be 
connected to slave units.) / If indoor unit models with louvres and 
models without louvres have been connected together, use an 
indoor unit with louvres as the master unit.
- The remote control termostat can also be set.
- Optional circuit boards can only be installed to the master unit.
- Setting the master unit and slave units can also be carried out 
manually by using DIP switches. However, manual settings will 
always take priority. If you have made manual settings but would 
like to return to using automatic settings, set all slave unit DIP 
switches (refer to the table below) to the OFF position, and then 
press the ADDRESS RESET button on the outdoor unit (SW3 on 
the outdoor unit printed circuit board). / (Do not mix manual 
settings and automatic settings.)