remote control will be set as the master. If the power source is 
installed to indoor units and outdoor units separately, turn on the 
switch by following the procedure: outdoor unit, then indoor unit 
with control, and finally other indoor units.
When the slave units do not operate (when address cannot be set) 
/  
Reset the address by following the procedure:
A. After making sure that dip-switches No. 1 to 4 and No. 8 are 
OFF, stop the operation.
B. Push address reset button (SW3) on the outdoor unit PC board 
for 4 seconds. Self-diagnosis LED No. 2 to 8 will start blinking 
in order. And when all 7 pieces of LEDs (No. 2 ~ 8) are 
illuminated, the address for the slave unit has been reset.
Important
: 
The address for the group control 
cannot be reset, using the above 
mentioned procedure.
2. Manual address setting (by dip-switch DSW1) / When setting the 
address manually, set the dip-switch of the PC board of the indoor 
unit as follows:
130