Important
: 
The address for the Twin/Triple 
control cannot be reset, using the 
above mentioned procedure.
2. Manual address setting (by dip-switch DSW1) / When setting the 
address manually, set the dip-switch of the PC board of the indoor 
unit as follows:
3. Manual address setting (by dip-switch DSW1) / When setting the 
address manually, set the dip-switch of the PC board in the indoor 
unit as follows:
 Procedures of deleting memory for twin/triple control system 
1. Switch off the main power supply.
2. Set the No. 8 pin of dip switch (DSW1) at the indoor unit’s P.C. 
board to “ON” position.
3. Switch on the main power supply for a minute and then turn it off.
4. Set the No. 8 pin of dip switch (DSW1) to “OFF” position.
 Procedures of deleting memory for group control system 
1. Switch off the main power supply.
2. Set the No. 1 until No. 4 pin of dip switch (DSW1) at the indoor 
unit’s P.C. board to “ON” position. / (Make sure No. 8 pin of dip 
switch (DSW1) is at “OFF” position)
3. Switch on the main power supply for a minute and then turn it off.
4. Set the No. 1 pin until No. 4 pin of dip switch (DSW1) to “OFF” 
132