RATED COOLING CAPACITY, RATED COOLING POWER / CONSUMPTION
MODEL NAME
RATED COOLING STANDARD
CAPACITY (kW) POWER CONSUMPTION (kW)
CS-A24BD2P/CU-A24BBP5 6.50 2.59
CS-A28BD2P/CU-A28BBP5 7.30 2.69
CS-A28BD2P/CU-A28BBP8 7.30 2.69
CS-A34BD2P/CU-A34BBP5 10.45 3.95
CS-A34BD2P/CU-A34BBP8 10.45 3.65
CS-A43BD2P/CU-A43BBP8 13.00 4.53
CS-A50BD2P/CU-A50BBP8 14.50 5.10
CS-A24BD2P/CU-C24BBP5 6.50 2.59
CS-A28BD2P/CU-C28BBP5 7.30 2.69
CS-A28BD2P/CU-C28BBP8 7.30 2.69
CS-A34BD2P/CU-C34BBP5 10.45 3.95
CS-A34BD2P/CU-C34BBP8 10.45 3.65
CS-A43BD2P/CU-C43BBP8 13.00 4.53
CS-A50BD2P/CU-C50BBP8 14.50 5.10
- Calculation of actual cooling capacity and power consumption
Example / CS-A28BD2P / CU-C28BBP8
- Calculation of the actual cooling capacity and power consumption for the following cooling
conditions: Indoor temperature of 18°C (wet-bulb temperature) and outdoor temperature of 40°C
(dry-bulb temperature).
Calculation method
- Find the cooling capacity ratio and power consumption ratio from the cooling capacity graph and
power consumption graph for model CS-A28BD2P / CU-C28BBP8.
137