1. The cooling capacity ratio indicated at the intersection between an outdoor unit heat exchanger
inlet air temperature of 40°C on the horizontal axis and an indoor unit heat exchanger inlet
temperature on 18°C is 0.92.
2. The cooling power consumption ratio from the same intersection on the power consumption
graph is 1.02.
- Thus, / Actual cooling capacity = cooling capacity ratio x rated cooling = 0.92 x 7.80 = 7.18 (kW)
Actual cooling power consumption = cooling power consumption x rated power consumption =
1.02 x 2.70 = 2.75 (kW)
15.2. PERFORMANCE DATA
Model
CS-A24BD2P/CU-A24BBP5, CS-A24BD2P/CU-C24BBP5
COOLING PERFORMANCE
138