COOLING CORRECTION FACTORS
EVAP. AIR FLOW m
3
/
min (l/s)
32 (533) 36 (600) 40 (666) 44 (733)
SHC Sensible Heat
Capacity
0.91 0.95 1 1.05
TC Total Cooling
Capacity
0.93 0.97 1 1.03
Model
CS-A50BD2P/CU-A50BBP8, CS-A50BD2P/CU-C50BBP8
COOLING PERFORMANCE
Ambient Temperature Air Entering Condenser (°C D.B.)
Return 25°C 30°C 35°C 40°C 45°C
Air TC SHC IPT TC SHC IPT TC SHC IPT TC SHC IPT TC SHC IPT
D.B. W.B. kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
17 15.27 14.20 4.42
14.6813.94
4.74
13.9413.67
5.06
13.0613.06
5.39
12.0412.04
5.66
23 19 16.00 12.32 4.74
15.4112.18
5.06
14.6811.89
5.39
13.9411.57
5.72
13.0611.10
5.98
22 17.32 9.53 5.28
16.73
9.54 5.55
16.00
9.44 5.88
15.27
9.31 6.14
14.38
9.06 6.47
17 15.17 14.11 4.42
14.5813.86
4.74
13.8613.58
5.06
12.9812.98
5.39
11.9611.96
5.66
25 19 15.90 12.24 4.74
15.3112.10
5.06
14.5811.81
5.39
13.8611.50
5.72
12.9811.03
5.98
22 17.21 9.47 5.28
16.63
9.48 5.55
15.90
9.38 5.88
15.17
9.25 6.14
14.29
9.00 6.47
17 15.08 14.02 4.42
14.5013.78
4.74
13.7813.50
5.06
12.9112.91
5.39
11.8911.89
5.66
27 19 15.81 12.17 4.74
15.2312.03
5.06
14.5011.75
5.39
13.7811.43
5.72
12.9110.97
5.98
22 17.11 9.41 5.28
16.53
9.42 5.55
15.81
9.32 5.88
15.08
9.20 6.14
14.21
8.95 6.47