2. For Heating Mode operation, the compressor operating frequency is regulated in accordance to outdoor air temperature as
shown in the below figures. This control will begin 50 seconds after the compressor starts.
8.2.14. Deodorizing Control
This type of control is applicable on Cooling Mode and Soft Dry Mode operation only.
1. During cooling or soft dry operation with automatic fan speed, the unit will operate as state below for deodorizing purpose.
2. When compressor is in operation, the steps follow: 1 2 3.
3. When compressor stops operation, the steps follow: 4 5 4 5
4. If the compressor still stops operation after three minutes, the step will start from 4.
5. This control is not applicable during sleep shift operation, ON timer preparation and anti-freezing control.