Model
Indoor CS-E18RKUAW CS-E24RKUAW
Outdoor CU-E18RKUA CU-E24RKUA
DRY BULB WET BULB DRY BULB WET BULB
Indoor Operation Range
(Cooling) (°F / °C)
Maximum 89.6 / 32 73.4 / 23 89.6 / 32 73.4 / 23
Minimum 60.8 / 16 51.8 / 11 60.8 / 16 51.8 / 11
Outdoor Operation Range
(Cooling) (°F / °C)
Maximum 114.8 / 46 78.8 / 26 114.8 / 46 78.8 / 26
Minimum 0 / -17.8 - / - 0 / -17.8 - / -
Indoor Operation Range
(Heating) (°F / °C)
Maximum 86.0 / 30 - / - 86.0 / 30 - / -
Minimum 60.8 / 16 - / - 60.8 / 16 - / -
Outdoor Operation Range
(Heating) (°F / °C)
Maximum 75.0 / 24 64.4 / 18 75.0 / 24 64.4 / 18
Minimum -4 / -20 -5.8 / -21 -4 / -20 -5.8 / -21
1. Cooling capacities are based on indoor temperature of 80°F DRY BULB, 67°F WET BULB and outdoor air temperature of 95°F DRY BULB,
75°F WET BULB.
2. Heating capacities are based on indoor temperature of 70°F DRY BULB, 60°F WET BULB and outdoor air temperature of 47°F DRY BULB,
43°F WET BULB.
3. Specifications are subjected to change without prior notice for further improvement.