117
20.1.3 CS-E18RKUAW CU-E18RKUA
Rated frequency (compressor speed is fixed during forced heating or cooling for capacity measurement and
diagnosis purpose)
Indoor (°C / °F) Outdoor (°C / °F)
DB WB -20 (-4) -10 (14) 0 (32) 5 (41)
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
27
(80.6)
19 (66.2) 21188 17930 935 21167 17913 924 21141 18234 896 21082 17831 888
22 (71.6) 24306 14656 817 24282 14641 807 23146 14323 936 21589 13429 934
23
(73.4)
16 (60.8) 18646 18460 1032 18628 18442 1019 19803 19605 849 18879 18690 941
18 (64.4) 20846 13794 945 20825 13780 933 23204 14860 739 21619 13003 982
20
(68)
13 (55.4) 16414 16250 1024 16398 16234 1011 16292 16129 672 15704 15547 803
16 (60.8) 16372 12160 1182 16356 12148 1168 17139 12557 699 18527 13408 689
Indoor (°C / °F) Outdoor (°C / °F)
DB WB 16 (60.8) 25 (77) 35 (95) 46 (114.8)
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
27
(80.6)
19 (66.2) 21000 18063 876 18377 16061 1195 17197 15993 1300 11804 10978 1169
22 (71.6) 21726 14368 879 19983 12710 1208 18977 9991 1317 13026 6858 1184
23
(73.4)
16 (60.8) 19472 19278 876 17002 16832 1172 15737 15580 1373 10802 10694 1234
18 (64.4) 21253 13726 878 18690 12233 1185 17325 11865 1398 11892 8144 1257
20
(68)
13 (55.4) 17023 16853 734 15925 15765 1171 14512 14366 1349 9961 9861 1212
16 (60.8) 19378 15270 1189 19083 13310 1503 16210 6590 1469 11126 4523 1321
20.1.4 CS-E24RKUAW CU-E24RKUA
Rated frequency (compressor speed is fixed during forced heating or cooling for capacity measurement and
diagnosis purpose)
Indoor (°C / °F) Outdoor (°C / °F)
DB WB -20 (-4) -10 (14) 0 (32) 5 (41)
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
27
(80.6)
19 (66.2) 29512 24706 1691 29483 24681 1670 29446 25124 1621 29365 24568 1606
22 (71.6) 33855 20194 1477 33821 20174 1459 32240 19735 1692 30071 18504 1688
23
(73.4)
16 (60.8) 25972 25712 1866 25946 25686 1843 27583 27307 1534 26296 26033 1701
18 (64.4) 29036 19007 1708 29006 18988 1687 31474 20475 1335 30112 17917 1775
20
(68)
13 (55.4) 22863 22634 1851 22840 22612 1828 22693 22466 1214 21873 21654 1451
16 (60.8) 22804 16755 2137 22781 16738 2111 23873 17302 1263 25806 18475 1246
Indoor (°C / °F) Outdoor (°C / °F)
DB WB 16 (60.8) 25 (77) 35 (95) 46 (114.8)
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
27
(80.6)
19 (66.2) 29250 24889 1584 25596 22130 2159 23953 22037 2350 16441 15126 2113
22 (71.6) 30261 19797 1589 27833 17513 2183 26432 13767 2381 18143 9449 2140
23
(73.4)
16 (60.8) 27122 26851 1584 23682 23445 2119 21920 21700 2481 15046 14895 2231
18 (64.4) 29602 18912 1588 26032 16855 2141 24131 16348 2527 16563 11221 2272
20
(68)
13 (55.4) 23711 23474 1326 22181 21959 2117 20212 20010 2438 13874 13735 2192
16 (60.8) 26991 21041 2149 26580 18340 2717 22578 9080 2655 15497 6233 2387
TC : Total capacity (BTU)
SHC: Sensible Heat Capacity (BTU)
IP: Input Power (Watt)