Operating Instructions
Air Conditioner
Panasonic Corporation
1006 Kadoma, Kadoma City, Osaka, Japan
WEB-ACXF55-29830-EN
Model No.
INDOOR UNIT
Middle Static Pressure Duct
(Type F3)
S-15MF3E5B S-60MF3E5B
S-22MF3E5B S-73MF3E5B
S-28MF3E5B S-90MF3E5B
S-36MF3E5B S-106MF3E5B
S-45MF3E5B S-140MF3E5B
S-56MF3E5B S-160MF3E5B
● Connectable outdoor unit lineup
OUTDOOR UNIT
Refrigerant type : R32
mini VRF (Type LZ2)
ENGLISH
Before operating the unit, read these operating instructions thoroughly and
keep them for future reference.
Middle Static Pressure Duct
(Type F3)
<At horizontal installation>
<At vertical installation>
01_330751_EN.indb 1 2021/5/27 10:36:17

Questions and Answers

Overview

This document provides operating instructions for the Panasonic Middle Static Pressure Duct (Type F3) indoor unit and mini VRF (Type LZ2) outdoor unit, which utilize R32 refrigerant. It covers safety precautions, product information, names of parts, maintenance, troubleshooting, and specifications.

Function Description

The Panasonic Middle Static Pressure Duct (Type F3) is a commercial air conditioner indoor unit designed to provide comfortable room conditions. It incorporates a biocidal product that generates ionized air to deactivate bacteria and viruses, inhibit mold growth on surfaces, and reduce odors. The unit is designed for either horizontal installation in the ceiling with rear side air intake or vertical installation.

The mini VRF (Type LZ2) outdoor unit works in conjunction with the indoor unit as part of a variable refrigerant flow (VRF) system. It uses R32 refrigerant, which is a flammable refrigerant.

Important Technical Specifications

Indoor Unit (Middle Static Pressure Duct - Type F3)

Power Source: 220-230-240 V~ 50-60 Hz

Cooling Capacity (kW / BTU/h):

  • S-15MF3E5B: 1.5 kW / 5,100 BTU/h
  • S-22MF3E5B: 2.2 kW / 7,500 BTU/h
  • S-28MF3E5B: 2.8 kW / 9,600 BTU/h
  • S-36MF3E5B: 3.6 kW / 12,300 BTU/h
  • S-45MF3E5B: 4.5 kW / 15,400 BTU/h
  • S-56MF3E5B: 5.6 kW / 19,100 BTU/h
  • S-60MF3E5B: 6.0 kW / 20,500 BTU/h
  • S-73MF3E5B: 7.3 kW / 24,900 BTU/h
  • S-90MF3E5B: 9.0 kW / 30,700 BTU/h
  • S-106MF3E5B: 10.6 kW / 36,200 BTU/h
  • S-140MF3E5B: 14.0 kW / 47,800 BTU/h
  • S-160MF3E5B: 16.0 kW / 54,600 BTU/h

Heating Capacity (kW / BTU/h):

  • S-15MF3E5B: 1.7 kW / 5,800 BTU/h
  • S-22MF3E5B: 2.5 kW / 8,500 BTU/h
  • S-28MF3E5B: 3.2 kW / 10,900 BTU/h
  • S-36MF3E5B: 4.2 kW / 14,300 BTU/h
  • S-45MF3E5B: 5.0 kW / 17,100 BTU/h
  • S-56MF3E5B: 6.3 kW / 21,500 BTU/h
  • S-60MF3E5B: 7.1 kW / 24,200 BTU/h
  • S-73MF3E5B: 8.0 kW / 27,300 BTU/h
  • S-90MF3E5B: 10.0 kW / 34,100 BTU/h
  • S-106MF3E5B: 11.4 kW / 38,900 BTU/h
  • S-140MF3E5B: 16.0 kW / 54,600 BTU/h
  • S-160MF3E5B: 18.0 kW / 61,400 BTU/h

Sound Pressure Level (dB(A)):

  • High: 31-43 dB(A) (depending on model)
  • Medium: 28-37 dB(A) (depending on model)
  • Low: 20-33 dB(A) (depending on model)

Sound Power Level (dB(A)):

  • High: 54-66 dB(A) (depending on model)
  • Medium: 51-60 dB(A) (depending on model)
  • Low: 43-56 dB(A) (depending on model)

Unit Dimensions (H×W×D):

  • S-15MF3E5B to S-90MF3E5B: 250×800×730 mm or 250×1,000×730 mm
  • S-106MF3E5B to S-160MF3E5B: 250×1,400×730 mm

Net Weight:

  • S-15MF3E5B to S-56MF3E5B: 26 kg
  • S-60MF3E5B to S-90MF3E5B: 31 kg
  • S-106MF3E5B to S-160MF3E5B: 40 kg

Operation Condition Temperature Range:

  • Cooling mode: 14°C-25°C WB
  • Heating mode: 16°C-30°C DB

Outdoor Unit (mini VRF - Type LZ2)

Power Source:

  • 1-phase models: 220-230-240 V~ 50 Hz
  • 3-phase models: 380-400-415 V 3N~ 50 Hz

Cooling Capacity (kW / BTU/h):

  • 4 HP: 12.1 kW / 41,300 BTU/h
  • 5 HP: 14.0 kW / 47,800 BTU/h
  • 6 HP: 15.5 kW / 52,900 BTU/h
  • 8 HP: 22.4 kW / 76,500 BTU/h
  • 10 HP: 28.0 kW / 95,600 BTU/h

Heating Capacity (kW / BTU/h):

  • 4 HP: 12.5 kW / 42,700 BTU/h
  • 5 HP: 16.0 kW / 54,600 BTU/h
  • 6 HP: 16.5 kW / 56,300 BTU/h
  • 8 HP: 25.0 kW / 85,300 BTU/h
  • 10 HP: 28.0 kW / 95,600 BTU/h

Sound Pressure Level (Cooling / Heating) (dB(A)):

  • 4 HP: 52 / 54 dB(A)
  • 5 HP: 53 / 56 dB(A)
  • 6 HP: 54 / 56 dB(A)
  • 8 HP: 60 dB(A)
  • 10 HP: 63 dB(A)

Sound Power Level (Cooling / Heating) (dB(A)):

  • 4 HP: 69 / 72 dB(A)
  • 5 HP: 70 / 74 dB(A)
  • 6 HP: 72 / 75 dB(A)
  • 8 HP: 81 dB(A)
  • 10 HP: 84 dB(A)

Unit Dimensions (H×W×D):

  • 4-6 HP: 996×980×370 mm
  • 8-10 HP: 1,500×980×370 mm

Net Weight:

  • 4-6 HP: 94 kg
  • 8-10 HP: 132-133 kg

Operation Condition Temperature Range:

  • Cooling mode: -10°C-52°C DB
  • Heating mode: -20°C-18°C WB

Usage Features

  • nanoe™ X Function: The indoor unit features nanoe™ X technology, which generates negative ions to provide healthier air by deactivating bacteria and viruses, inhibiting mold growth, and reducing odors. This function operates automatically upon purchase but can be turned off via the remote controller.
  • Remote Control Options: The system supports various remote controllers:
    • Wireless Remote Controller (Model No. CZ-RWS3, CZ-RWRC3)
    • Timer Remote Controller (Model No. CZ-RTC4)
    • High-spec Wired Remote Controller (Model No. CZ-RTC5B)
    • Wired Remote Controller (Model No. CZ-RTC6 series)
  • Automatic Operation Resumption: In case of a power failure, the unit will automatically resume operation with the settings prior to the power failure once power is restored.
  • Defrosting Operation: During heating, the unit may initiate a defrosting operation to melt frost on the outdoor unit. The indoor unit fan may stop or run at a very slow speed during this process, and "STANDBY" will be displayed. Heating operation resumes once the indoor heat exchanger warms up.
  • "DRY" Operation: In dry mode, once the room temperature reaches the set level, the outdoor unit cycles on and off automatically. The fan speed is set to "breeze" (light wind) when the room temperature is close to the set level.
  • Energy Saving Tips:
    • Avoid blocking air intake and outlet.
    • Use sunshades, blinds, or curtains during cooling to prevent direct sunlight.
    • Keep windows, doors, and other openings closed to prevent conditioned air from escaping.
    • Regularly clean the air filter.

Maintenance Features

  • Air Filter Maintenance: The air filter should be kept clean. Users are advised to consult their dealer or service center for cleaning.
  • Outdoor Unit Coil Cleaning: The internal coil and other components of the outdoor unit must be cleaned periodically by a dealer or service center.
  • Safety Precautions for Maintenance:
    • Always turn off the air conditioner and disconnect power before cleaning to prevent electric shock or injury from rotating fan parts.
    • Do not pour water on the indoor unit to avoid damaging internal components and electric shock.
    • Avoid using solvents or harsh chemicals, or very hot water on plastic parts, to prevent deformation or discoloration.
    • Exercise caution when cleaning metal edges and fins, as they can be sharp.
    • Use a firm stool or ladder for cleaning indoor units installed in high locations.
  • Refrigerant Leak Sensors (R32 specific): The indoor unit is equipped with R32 refrigerant leak sensors.
    • If leakage is detected, a P08 alarm and inspection mark will appear on the remote controller, and the indoor unit fan will run continuously to prevent refrigerant stagnation. In this event, do not turn off the ELCB, ventilate the room, and contact the service dealer immediately.
    • Alarms J03 or J05 indicate issues with the R32 refrigerant leak sensors. Contact the service dealer.
    • Alarms J04 or J06 indicate the end of life for the R32 refrigerant leak sensors, requiring replacement by a service dealer. Continuous use of deteriorated sensors may prevent proper leak detection.
  • Troubleshooting Guide: The manual provides a comprehensive troubleshooting section to help identify and resolve common issues such as noise, odors, water leaks, fan operation anomalies, and error codes. It advises contacting a dealer for issues like dirty internal units, refrigerant leaks, or sensor replacement.

Panasonic S-15MF3E5B Specifications