v
(3)  If an indoor unit is installed in each partitioned room and 
the refrigerant tubing is interconnected, the smallest room 
of course becomes the object. But when mechanical 
ventilation is installed interlocked with a gas leakage 
detector in the smallest room where the density limit is 
exceeded, the volume of the next smallest room becomes 
the object.
2.  The minimum indoor floor space compared with the 
amount of refrigerant is roughly as follows: (When the 
ceiling is 2.7 m high)
20100 30 40 60 70 80 90 10050
m
2
m
3
40.5
54.0
27.0
13.5
0.0
67.5
81.0
94.5
108.0
121.5
135.0
148.5
162.0
175.5
189.0
202.5
216.0
15
10
5
0
20
25
30
35
40
45
50
55
60
65
70
75
80
229.5
85
kg
 
Total amount of refrigerant
Range below the 
density limit of  
0.44 kg/m³ 
(Countermeasures 
not needed)
Range above the 
density limit of 
0.44 kg/m³
(Countermeasures 
needed)
Min. indoor volume
Min. indoor floor area
(when the ceiling is 2.7 m high)
Check of Density Limit
Check the amount of refrigerant in the system and 
floor space of the room according to the legislation on 
refrigerant drainage. If there is no applicable legislation, 
follow the standards described below.
The room in which the air conditioner is to be installed 
requires a design that in the event of refrigerant gas 
leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air conditioner, 
is safe, without the toxicity or combustibility of ammonia, and 
is not restricted by laws imposed to protect the ozone layer. 
However, since it contains more than air, it poses the risk of 
suffocation if its density should rise excessively. Suffocation 
from leakage of refrigerant is almost non-existent. With the 
recent increase in the number of high density buildings, 
however, the installation of multi air conditioner systems is 
on the increase because of the need for effective use of floor 
space, individual control, energy conservation by curtailing heat 
and carrying power, etc. 
Most importantly, the multi air conditioner system is able 
to replenish a large amount of refrigerant compared to 
conventional individual air conditioners. If a single unit of the 
multi air conditioner system is to be installed in a small room, 
select a suitable model and installation procedure so that if the 
refrigerant accidentally leaks out, its density does not reach the 
limit (and in the event of an emergency, measures can be made 
before injury can occur).
In a room where the density may exceed the limit, create an 
opening with adjacent rooms, or install mechanical ventilation 
combined with a gas leak detection device. The density is as 
given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
3
) 
< Density limit (kg/m
3
)
The density limit of refrigerant which is used in multi air 
conditioners is 0.44 kg/m
3
 (ISO 5149).
NOTE
1.  The standards for minimum room volume are as follows.
(1)  No partition (shaded portion)
(2)  When there is an effective opening with the adjacent room 
for ventilation of leaking refrigerant gas (opening without 
a door, or an opening 0.15% or larger than the respective 
floor spaces at the top or bottom of the door).
Outdoor unit
Refrigerant tubing
Indoor unit
Mechanical ventilation device – Gas leak detector
Refrigerant tubing
Outdoor unit
Indoor unit
Very 
small 
room
Small 
room
Medium 
room
Large room
00_291827_2WAY_Eng.indb   5 2017/7/5   13:41:24
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1.  Process tubing
●  Material: Use seamless phosphorous deoxidized copper tube for refrigeration. Wall thickness shall comply with the applicable 
legislation. The minimal wall thickness must be in accordance with the table below.
●  Tubing size: Be sure to use the sizes indicated in the table below. 
For the renewal tubing size, refer to the Technical Data.
●  Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).
●  When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
 
CAUTION
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to prevent dirt, 
moisture, or other foreign substances from entering. These substances can result in system 
malfunction.
Unit: mm 
Material Temper - O (Soft copper tube)
Copper tube
Outer diameter 6.35 9.52 12.7 15.88 19.05
Wall thickness 0.8 0.8 0.8 1.0 1.2
 
1-2.   Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refrigerant deterioration 
and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other 
impurities becomes more important than ever.
2.  Be sure to recharge the refrigerant only in liquid form.
2-1.  Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects in the unit.
2-2.  Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refrigerant and recharge 
the required total amount of new refrigerant after fixing the leak.
3.  Different tools required
3-1.  Tool specifications have been changed due to the characteristics of R410A.
  Some tools for R22- and R407C-type refrigerant systems cannot be used.
Item New tool?
R407C tools 
compatible 
with R410A?
Remarks
Manifold gauge 
Manifold gauge Yes  No  Types of refrigerant, refrigerating machine oil, 
and pressure gauge are different.
Charge hose Yes No  To resist higher pressure, material must be 
changed.
Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped 
with a check valve. If it has no check valve, 
purchase and attach a vacuum pump adapter.
Leak detector Yes  No  Leak detectors for CFC and HCFC that react to 
chlorine do not function because R410A contains 
no chlorine. Leak detectors for HFC134a can be 
used for R410A. 
Vacuum pump
Outlet
Inlet
Flaring oil  Yes  No  For systems that use R22, apply mineral oil 
(Suniso oil) to the flare nuts on the tubing to 
prevent refrigerant leakage. For machines that 
use R407C or R410A, apply synthetic oil (ether 
oil) to the flare nuts.
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
3-2.  Use R410A exclusive cylinder only.
Single-outlet valve 
(with siphon tube) 
Liquid refrigerant should be 
recharged with the cylinder 
standing on end as shown.
Valve
Liquid
00_291827_2WAY_Eng.indb   6 2017/7/5   13:41:24
SM830258-01_欧州向け_1fan_mini_VRF.indb   6 18/03/02   10:16:59