2.  SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
●  areas where leakage of flammable gas may be expected.
●  places where large amounts of oil mist exist.
●  direct sunlight.
●  locations near heat sources which may affect the 
performance of the unit.
●  locations where external air may enter the room directly. 
This may cause “condensation” on the air discharge ports, 
causing them to spray or drip water.
●  locations where the remote controller will be splashed with 
water or affected by dampness or humidity.
●  installing the remote controller behind curtains or furniture.
●  locations where high-frequency emissions are generated.
DO:
●  select an appropriate position from which every corner of the 
room can be uniformly cooled.
●  select a location where the ceiling is strong enough to 
support the weight of the unit.
●  select a location where tubing and drain pipe have the 
shortest run to the outdoor unit.
●  allow room for operation and maintenance as well as 
unrestricted air flow around the unit.
●  the limitation of the tubing length between the indoor and 
the outdoor units should be referred to the Installation 
Instructions of the outdoor unit.
●  allow room for mounting the remote controller about 1 m off 
the floor, in an area that is not in direct sunlight or in the flow 
of cool air from the indoor unit.
4-Way Cassette Type
Wall
indoor unit indoor unit
min. 1 m
min. 1 m
Over 2.5 m 
min. 3 m
Obstacles
Ceiling
1 m
1 m
1 m
1 m