5-30
5
F06 Inlet Temperature Sensor (C1) in Heat Exchanger Trouble
Error Detection Method
Error Diagnosis
1.
2.
In case of open or short
Outdoor unit control PCB failure
Replace PCB with a new one.
Is the connector properly connected to PCB?1-1
Is the resistor between the sockets infinity or 0Ω?1-2
2-1
1-2
Reconnect & check
Replace sensor.
2-1
Yes
No
1
Sensor
Trouble
2
Control
PCB
Failure
Yes
No