5-45
5
L04 Outdoor Unit Address Duplication
Error Detection Method
Error Diagnosis
It is judged an error when the identical self-address communication on the indoor and outdoor wirings is received over 5 times
within 3 minutes.
1.
2.
Are other outdoor units using a duplicate setting?1-1
2-1
2-2
Yes
No
2
When units are networked, first set the system address for each outdoor unit in the order
1-2-3 and then run auto address setting.
2-1
Run the auto address setting.
2-2
Installation
or setting
related
1
System
address
SM830231-02Single.indb45SM830231-02Single欧州.indb45 2014/09/1115:44:172014/09/1115:44:17