25
8-5. Test Run Using the Remote Controller
High-spec Wired Remote Controller (CZ-RTC5A)
(1) +EEPPRESSINGTHE
,
and buttons
simultaneously for 4 or more seconds.
4HEh-AINTENANCEFUNCvSCREENAPPEARSONTHE,#$
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel. Page [ ] Confirm
20:30 (THU)
(2) Press the or button to see each menu.
If you wish to see the next screen instantly, press the
or button.
3ELECTh4ESTRUNvONTHE,#$DISPLAYANDPRESSTHE
button.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel. Page [ ] Confirm
20:30 (THU)
Change the display from OFF to ON by pressing the
or button. Then press the button.
[ ] Confirm
Test run
Change
20:30 (THU)
Test run
ON
START
[]
20:30 (THU)
(1)
(1)
(4)
(3) Press the button. “TEST” will be displayed on the
,#$DISPLAY
TEST
START[]
20:30 (THU)
(4) Press the button. Test run will be started.
4ESTRUNSETTINGMODESCREENAPPEARSONTHE,#$DISPLAY
TEST
20:30 (THU)
COOL
MODE
Timer remote controller (CZ-RTC4)
(1) Press the remote controller
button for 4 seconds or longer.
Then press the
button.
●
“
vAPPEARSONTHE,#$DISPLAYWHILETHETESTRUNISINPROGRESS
●
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines.
Therefore use it only when performing the test run.)
(2)4HETESTRUNCANBEPERFORMEDUSINGTHE(%!4#//,OR&!.
operation modes.
NOTE
The outdoor units will not operate for approximately 3 minutes after the
power is turned ON and after operation is stopped.
(3) If correct operation is not possible, a code is displayed on the remote
CONTROLLER,#$DISPLAY
(3EETHESECTIONh4ABLEOF3ELF$IAGNOSTIC&UNCTIONSAND
Corrections” and correct the problem.)
(4) After the test run is completed, press the
button again.
Check that “
vDISAPPEARSFROMTHE,#$DISPLAY
(To prevent continuous test runs, this remote controller includes a timer
function that cancels the test run after 60 minutes.)
* If the test run is performed using the wired remote controller, operation
is possible even if the cassette-type ceiling panel has not been
installed. (“P09” display does not occur.)
26
8-6. Precautions
● Request that the customer be present when the test run is
performed. At this time, explain the operation manual and
have the customer perform the actual steps.
● "ESURETOPASSTHEMANUALSANDWARRANTYCERTIFICATETOTHE
customer.
● Check that the 220 – 240 V AC power is not connected to
the inter-unit control wiring connector terminal.
* If 220 – 240 V AC is accidentally applied, the indoor or
OUTDOORUNITCONTROL0#"FUSEWILLBLOWINORDERTOPROTECT
THE0#"#ORRECTTHEWIRINGCONNECTIONS2EMOVETHE
short connector connected to the OC side and reconnect
TOTHE%-'SIDEONTHEOUTDOORCONTROL0#"#UTTHE3!
OUTOFTHEOUTDOORUNITCONTROL0#"4HENDISCONNECTTHE
2P connectors (OC) that are connected to the indoor unit
0#"ANDREPLACETHEMWITH0CONNECTORS%-'
If operation is still not possible after changing the brown
connectors, cut off the jumper (indoor unit) or the varistor
INDOORUNITONTHE0#""ESURETOTURNTHEPOWER/&&
before performing this work.)
/UTDOORUNITCONTROL0#"
CN-EMG
SA1
)NDOORUNITCONTROL0#"
■
Type U2
Jumper
(JP040)
EMG (CN044, brown)
OC (CN040, blue)
■
Type T2
Jumper
(JP040)
EMG (CN044, brown)
OC
(CN040, blue)
Jumper
(JP040)
OC
(CN040, blue)
EMG (CN044, brown)
■
Type F1
OC
(CN040, blue)
Jumper
(JP003)
EMG
(CN044, brown)
■
Type N1
■
Type Y2
OC (CN040, blue)
EMG (CN044, brown)
Jumper (JP003)
■
Type K1
Jumper
(JP003)
EMG
(CN044, brown)
OC
(CN040, blue)
15