1-1. Unit Specifi cations
PE1
6. 4-Way Cassette 60×60 Type S-50PY2E5A / U-50PE1E5
INDOOR MODEL S-50PY2E5A
PANEL MODEL CZ-KPY3A / CZ-KPY3B
OUTDOOR MODEL U-50PE1E5
Branch pipe MODEL -
PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 / EN12102
POWER SUPPLY
ø, Hz 1ø 50Hz 1ø 50Hz
V 220 230 240 220 230 240 Min Max
C
O
O
L
I
N
G
CAPACITY
kW 5.0 5.0 5.0 1.5 5.6
BTU/h 17100 17100 17100 5100 19100
CURRENT A 0.35 7.80 7.50 7.20 - -
INPUT POWER
W 45 1.595k 1.595k 1.595k - -
TOTAL W - 1.640k 1.640k 1.640k 260 2.450k
ANNUAL CONSUMPTION
TOTAL kWh
*
4 - - - 820 820 820 - -
EER/EER CLASS
TOTAL(W/W)
*
5/("A"~"G")
- - - 3.04 3.04/B 3.04 5.77 2.29
Erp
*
6
Pdsign kW - - - - 5.0 -
SEER (W/W) - - - - 5.9 -
Annual consumption
kWh - - - - 297 -
Class - - - - A+ -
POWER FACTOR % - - - 93 92 92
NOISE INDOOR
(H/M/L)
dB-A 40/37/33
Power Level dB 55/52/48
NOISE OUTDOOR
(H/L)
dB-A 46/-
Power Level dB 65/-
H
E
A
T
I
N
G
CAPACITY
kW 5.6 5.6 5.6 1.5 6.3
BTU/h 19100 19100 19100 5100 21500
CURRENT A 0.35 8.60 8.20 7.90 - -
INPUT POWER
W 40 1.750k 1.750k 1.750k - -
TOTAL W - 1.790k 1.790k 1.790k 220 2.570k
COP/COP CLASS
TOTAL(W/W)
*
5/("A"~"G")
- - - 3.12 3.12/D 3.12 6.82 2.45
Erp
*
6
Pdsign kW - - - - 4.0 -
Tbivalen °C - - - - -10 -
SCOP (W/W) - - - - 3.8 -
Annual consumption
kWh - - - - 1474 -
Class - - - - A -
POWER FACTOR % - - - 92 93 92
NOISE INDOOR
(H/M/L)
dB-A 40/37/33 -
Power Level dB 55/52/48 -
NOISE OUTDOOR
(H/L)
dB-A - 50/-
Power Level dB - 69/-
EXTRA LOW TEMP
Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W) 0.40/55 12.0/2.46k 12.0/2.57k 12.0/2.68k
STARTING CURRENT(A)/COMP OUTPUT(W) - - - 8.60/0.9k 8.20/0.9k 7.90/0.9k
NETWORK IMPEDANCE (ΩMAX.) - -
FM OUTPUT (W) 40 90
MOISTURE REMOVAL VOLUME L/h(Pt/h) 2.8 (5.9) -
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 11.1 / 9.8 / 8.5 (392) / (346) / (300)
HEAT m
3
/min (ft
3
/min) 11.1 / 9.8 / 8.7 (392) / (346) / (307)
O/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 30 (1059)
HEAT m
3
/min (ft
3
/min) 35 (1236)
REFRIGERANT TYPE, AMOUNT
g
(oz) R410A 1.65k (58.2)
P
R
O
D
I
M
HEIGHT : H mm(inch) 260<265 + 23> (10-1/4) 569 (22-13/32)
WIDTH : W mm(inch) 575<583> (22-21/32) 790 (31-7/64)
DEPTH : D mm(inch) 575<583> (22-21/32) 285 (11-7/32)
Panel : H×W×D mm 3A:31 × 700 × 700, 3B:31 × 625 × 625
-
P
A
C
D
I
M
HEIGHT : H mm 345 (13-19/32) 645
WIDTH : W mm 691 (27-7/32) 921
DEPTH : D mm 691 (27-7/32) 386
MASS
(NET) k
g
(lb) 18 (40) 42 (93)
(GROSS) k
g
(lb) 23 (51) 46 (101)
Panel : (NET) k
g
(lb) 2.4 (5.3) -
LAYERS LIMIT (actually) 11(12) 4(5)
Operation
Condition
Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C
Heat (DBT) 16°C ~ 30°C -20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2) (Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0 (16.4) fl ared type, 5.0 (16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 40 (16.4 ~ 131.2)
I/D&O/D HEIGHT DIFFERENCE m (ft)
15(OD located lower)/30(OD located higher) (49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
20 (0.215)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30 (98.4)
*1: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2: If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7
°C
dry bulb and -8
°C
wet-bulb temperatures with rated voltage 230V
shall be used.
*3: Network Impedance shall be applicable for EUROPE and CHINA models.
*4: The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5: EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6: SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche
data indicates in an attached sheet.
SM830231-02Single欧州.indb132SM830231-02Single欧州.indb132 2014/09/1913:21:092014/09/1913:21:09