5-46
5
Was EEPROM replaced when PC board was replaced?1-1
2-1
Replace EEPROM
Yes
No
1 Check the
control
PC board
L10 Outdoor Unit Capacity not Set or Invalid
Error Detection Method
Error Diagnosis
1.
2.
Set an applicable capacity value on the item code 81 display of maintenance remote
controller.
2-1
2 Installation
or setting
related
It is judged an error when outdoor unit capacity not yet setup or systematically unauthorized setting.
Check : Connect the outdoor maintenance remote controller and check whether item code 81 outdoor capacity value
shows “0” or unauthorized capacity is set on the detailed settings mode display of the outdoor EEPROM.
If the capacity value of the item code 81 with the outdoor maintenance remote controller is incorrect, recorrect and
set it again.
* After setting the capacity value, be sure to reset the power supply switches of both indoor and outdoor units.
SM830231-02Single.indb46SM830231-02Single欧州.indb46 2014/09/1115:44:182014/09/1115:44:18