1-235
1
1-6.  Noise Criterion Curves
(A)   Indoor Units:
4-Way Cassette Type
REMARKS:
NOTE
1. Value obtained in the actual place where the unit is installed 
may be slightly higher than the values shown in this graph 
because of the conditions of operation, the structure of the 
building, the background noise and other factors.
2. The test results were obtained from an anechoic room.
To evaluate “Noise level” the maximum number of the measured 
OCTAVE BAND SOUND PRESSURE LEVEL is used.
Read the number on each BAND CENTER FREQUENCIES 
(horizontal axis) ranging from 63 Hz to 8000 Hz and select the 
maximum value (vertical axis) among them.
Low
High
Octave Band Level (dB)
*0dB = 0.0002 µbar
Octave Band Level (dB)
*0dB = 0.0002 µbar
Frequency at center of sound pressure band (Hz)
Frequency at center of sound pressure band (Hz)
10
20
30
40
50
60
63 125 250 500 1000 2000 4000 8000
NC-40
NC-50
NC-30
NC-20
NC-60
10
20
30
40
50
60
63 125 250 500 1000 2000 4000 8000
NC-40
NC-60
NC-50
NC-30
NC-20
MODEL
SOUND LEVEL
CONDITION
SOURCE
: S-125PU1E5A
: High
Low
45 dB(A)
33 dB(A)
: Under the unit 1.5m
: 220-230-240V, 1 phase, 50Hz
MODEL
SOUND LEVEL
CONDITION
SOURCE
: S-140PU1E5A
: High
Low
46 dB(A)
34 dB(A)
: Under the unit 1.5m
: 220-230-240V, 1 phase, 50Hz
MODEL
SOUND LEVEL
CONDITION
SOURCE
: S-71PU1E5A 
: High
Low
37 dB(A)
28 dB(A)
: Under the unit 1.5m
: 220-230-240V, 1 phase, 50Hz
Octave Band Level (dB)
*0dB = 0.0002 µbar
Octave Band Level (dB)
*0dB = 0.0002 µbar
Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz)
10
20
30
40
50
60
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
10
20
30
40
50
60
63 125 250 500 1000 2000 4000 8000
NC-40
NC-60
NC-50
NC-30
NC-20
MODEL
SOUND LEVEL
CONDITION
SOURCE
: S-100PU1E5A
: High
Low
44 dB(A)
32 dB(A)
: Under the unit 1.5m
: 220-230-240V, 1 phase, 50Hz
Approximate 
minimum 
audible limit 
for continuous 
noise
Approximate 
minimum 
audible limit 
for continuous 
noise
Approximate 
minimum 
audible limit 
for continuous 
noise
Approximate 
minimum 
audible limit 
for continuous 
noise
SM830231-02Single欧州.indb235SM830231-02Single欧州.indb235 2014/09/1913:21:392014/09/1913:21:39