Operating Instructions
Air Conditioner
Model No.
OUTDOOR UNIT
2WAY (Type ME2 )
U-8ME2H7
U-10ME2H7
U-12ME2H7
U-14ME2H7
U-16ME2H7
U-8ME2H7E*
U-10ME2H7E*
U-12ME2H7E*
U-14ME2H7E*
U-16ME2H7E*
U-18ME2H7 U-18ME2H7E*
U-20ME2H7 U-20ME2H7E*
* Salt-air damage resistant
Connectable indoor unit lineup
This booklet is the operating instructions
for outdoor unit. Regarding the indoor
unit, see the operating instructions
supplied with the indoor unit.
INDOOR UNIT
1-Way Cassette
2-Way Cassette
4-Way Cassette
4-Way Cassette 60 × 60
Wall-Mounted
Ceiling
Low Silhouette Ducted
Slim Low Static Ducted
High Static Pressure Ducted
Floor Standing
Concealed Floor Standing
Slim Type Ducted
Fresh Air intake Duct
ACXF55-00601
* Shows 2WAY (Type ME2)
ENGLISH
2 ~ 5
Before operating the unit, read these operating instructions thoroughly and
keep them for future reference.
B.MALAYSIA
6 ~ 9
Sebelum mengendalikan unit, bacalah arahan pengendalian ini sepenuhnya
dan simpan untuk rujukan masa depan.
中文
10 ~13
在操作本裝置前,請完整詳閱此使用說明書,並保存此說明書以備日後參考。

14 ~ 17


B.INDONESIA
18 ~ 21
Sebelum mengoperasikan unit, baca petunjuk pengoperasian ini secara
menyeluruh dan simpan untuk referensi mendatang.
ESPAÑOL
22 ~ 25
Antes de operar la unidad, lea atentamente estas instrucciones de
funcionamiento y guárdelas para futuras consultas.
PORTUGUÊS
26 ~ 29
Antes de utilizar o aparelho, leia completamente este manual de instruções
e guarde-o para futuras referências.
РУССКИЙ
30 ~ 33
Перед использованием этого устройства внимательно прочитайте
настоящую инструкцию по эксплуатации и сохраните ее для
дальнейших справок.
УКРАЇНСЬКА
34 ~ 37
Уважно прочитайте цю інструкцію з експлуатації перед тим, як
увімкнути пристрій, та збережіть її на майбутнє.
ENGLISH
B.MALAYSIA

B
.INDONESIA
ESPAÑOL
PORTUGUÊS
РУССКИЙ
УКРАЇНСЬКА
Panasonic Corporation
1006, Oaza Kadoma, Kadoma City,
Osaka 571-8501, Japan
00_340129_all.indb 1 2022/7/7 10:02:44
Question and Answer IconNeed help?

Do you have a question about the Panasonic U-8ME2H7E Series and is the answer not in the manual?

Overview

This document provides operating instructions for a Panasonic commercial air conditioner outdoor unit, specifically the 2WAY (Type ME2) models. It covers various aspects from safety and installation to technical specifications and maintenance.

Function Description

The Panasonic 2WAY (Type ME2) air conditioner outdoor unit is designed to provide comfortable room conditions for commercial use in shops, light industry, farms, or by lay persons. It functions as part of a split-system air conditioning system, working in conjunction with various indoor unit types to deliver cooling and heating. The system utilizes R410A refrigerant, a fluorinated greenhouse gas, and is designed for efficient operation within specified temperature ranges.

Important Technical Specifications

The outdoor unit models covered include:

  • U-8ME2H7 / U-8ME2H7E*
  • U-10ME2H7 / U-10ME2H7E*
  • U-12ME2H7 / U-12ME2H7E*
  • U-14ME2H7 / U-14ME2H7E*
  • U-16ME2H7 / U-16ME2H7E*
  • U-18ME2H7 / U-18ME2H7E*
  • U-20ME2H7 / U-20ME2H7E*

(* indicates salt-air damage resistant models)

Power Source: 380-400-415 V 3N~ 50 Hz, 380-400 V 3N~60 Hz

Cooling Capacity:

  • U-8ME2H7: 22.4 kW (76,500 BTU/h)
  • U-10ME2H7: 28.0 kW (95,600 BTU/h)
  • U-12ME2H7: 33.5 kW (114,300 BTU/h)
  • U-14ME2H7: 40.0 kW (136,500 BTU/h)
  • U-16ME2H7: 45.0 kW (153,600 BTU/h)
  • U-18ME2H7: 50.0 kW (170,600 BTU/h)
  • U-20ME2H7: 56.0 kW (191,100 BTU/h)

Heating Capacity:

  • U-8ME2H7: 25.0 kW (85,300 BTU/h)
  • U-10ME2H7: 31.5 kW (107,500 BTU/h)
  • U-12ME2H7: 37.5 kW (128,000 BTU/h)
  • U-14ME2H7: 45.0 kW (153,600 BTU/h)
  • U-16ME2H7: 50.0 kW (170,600 BTU/h)
  • U-18ME2H7: 56.0 kW (191,100 BTU/h)
  • U-20ME2H7: 63.0 kW (215,000 BTU/h)

Sound Pressure Level:

  • U-8ME2H7: 53.0 dB(A)
  • U-10ME2H7: 56.0 dB(A)
  • U-12ME2H7: 57.0 dB(A)
  • U-14ME2H7: 58.0 dB(A)
  • U-16ME2H7: 61.0 dB(A)
  • U-18ME2H7: 59.0 dB(A)
  • U-20ME2H7: 59.0 dB(A)

Sound Power Level:

  • U-8ME2H7: 74.0 dB(A)
  • U-10ME2H7: 77.0 dB(A)
  • U-12ME2H7: 78.0 dB(A)
  • U-14ME2H7: 79.0 dB(A)
  • U-16ME2H7: 82.0 dB(A)
  • U-18ME2H7: 80.0 dB(A)
  • U-20ME2H7: 80.0 dB(A)

Unit Dimensions (H×W×D):

  • U-8ME2H7, U-10ME2H7: 1842×770×1000 mm
  • U-12ME2H7, U-14ME2H7, U-16ME2H7: 1842×1180×1000 mm
  • U-18ME2H7, U-20ME2H7: 1842×1540×1000 mm

Net Weight:

  • U-8ME2H7, U-10ME2H7: 210 kg
  • U-12ME2H7, U-14ME2H7, U-16ME2H7: 270 kg (U-12ME2H7), 315 kg (U-14ME2H7, U-16ME2H7)
  • U-18ME2H7, U-20ME2H7: 375 kg

Refrigerant Type: R410A (GWP value: 2088)

Operating Conditions (Outdoor Temperature Range):

  • Cooling: -10°C ~ 52°C (DBT) / -10°C ~ 43°C (DBT)*1
  • Heating: -25°C ~ 18°C (WBT) (*1: Maximum allowable temperature is reduced to 43°C when using existing R22 pipe.)

Operating Conditions (Indoor Temperature Range):

  • Cooling: 14°C ~ 25°C (WBT)
  • Heating: 16°C ~ 30°C (DBT)

Rated Conditions:

  • Cooling: Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.
  • Heating: Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.

The outdoor unit is compatible with a variety of indoor unit types, including:

  • 1-Way Cassette
  • 2-Way Cassette
  • 4-Way Cassette
  • 4-Way Cassette 60 × 60
  • Wall-Mounted
  • Ceiling
  • Low Silhouette Ducted
  • Slim Low Static Ducted
  • High Static Pressure Ducted
  • Floor Standing
  • Concealed Floor Standing
  • Slim Type Ducted
  • Fresh Air intake Duct

Usage Features

The air conditioner is operated via optional remote controllers:

  • Wireless Remote Controller: Model No. CZ-RWS3, CZ-RWSK2 (Infrared Remote Controller)
  • Timer Remote Controller: Model No. CZ-RTC4 (for all indoor units)
  • High-spec Wired Remote Controller: Model No. CZ-RTC5B (for all indoor units)

Installation:

  • Must be installed by qualified technicians according to provided instructions.
  • Voltage of electrical supply must match the nameplate.
  • Avoid locations with smoke, combustible gas, extremely high temperatures (e.g., greenhouses), or excessive heat-generating objects.
  • For salt-air damage resistant models, avoid direct exposure to salty sea water or sulphurous air near spas to prevent heavy corrosion.
  • All wiring must conform to local electrical codes and be performed by a qualified electrician.
  • Each unit must be properly grounded.
  • Operation Preparation: Turn on the power mains 5 hours before starting operation (for warm-up) and keep it ON for continuous use.

Safety Precautions:

  • Confirm specified refrigerant type with an authorized dealer.
  • The unit has no ventilator for fresh air intake; open doors/windows frequently when using gas/oil heating appliances in the same room.
  • Do not use or store flammable liquids/vapors near the unit.
  • Do not use in potentially explosive atmospheres.
  • Do not touch the unit with wet hands.
  • Do not insert fingers or objects into indoor/outdoor units; rotating parts can cause injury.
  • Refrigerant in contact with flame produces toxic gas.
  • Disconnect power before cleaning/servicing.
  • In emergency, pull power plug, switch off breaker, or power disconnecting means.
  • Cleaning of internal/external units should be done by authorized dealers/specialists.
  • Do not repair malfunctions yourself; contact sales/service dealer.
  • Provide an exclusive power outlet with overcurrent protection (ELCB or RCD).
  • Ensure full disconnection means in fixed wiring.
  • Unit must be grounded to prevent insulation failure hazards.
  • Do not use modified, joint, extension, or unspecified cords.
  • Stop using immediately if abnormality/failure occurs (e.g., ELCB trips frequently, unit doesn't start, power disconnects when cord moves, burnt odor, abnormal noise, deformed/hot body, water leaks, hot power cord/plug, uncontrolled fan speed, unit stops immediately after starting, fan doesn't stop after operation stops). Contact local dealer for repair.
  • Keep fire alarm and air outlet at least 1.5m away.
  • Do not overcool/overheat rooms with babies or invalids present.
  • Use ON/OFF button, not main power switch, to turn unit on/off.
  • Do not stick objects into outdoor unit air outlet or fan case.
  • Do not touch air inlet or sharp aluminum fins of outdoor unit.
  • Do not sit or step on the unit.

Maintenance Features

  • Adjusting Airflow Direction: Refer to the operating instructions attached to the indoor unit.
  • Maintenance: Refer to the operating instructions attached to the indoor unit.
  • Troubleshooting: Refer to the operating instructions attached to the indoor unit.
  • Long-term Non-use: Pull off the power plug, switch off the breaker, or switch off the power disconnecting means to isolate the air conditioner from the main power supply.
  • Refrigerant Leak Inspections: Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Contact your local dealer for more information.
  • E-waste Management (India): All electrical and electronic products must be handed over only to authorized recyclers for disposal. Products should not be opened by users, re-sold to unauthorized agencies, or mixed with household waste. Replaced spare parts should not be kept in exposed areas. Do not donate old electronic items or dispose of them in garbage bins. Do not give e-waste to informal sectors.