EasyManua.ls Logo

Panasonic WH-SDC07C3E5 - Page 97

Panasonic WH-SDC07C3E5
166 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
97
17.5.3. Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the indoor refrigerant liquid temperature
sensor are used to determine sensor error.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.

Table of Contents