F568561
Operating Instructions
Air-to-Water Heatpump
Model No.
Indoor Unit
Outdoor Unit
WH-SDC09C3E8 WH-UD09CE8
WH-SDC12C9E8 WH-UD12CE8
WH-SDC14C9E8 WH-UD14CE8
WH-SDC16C9E8 WH-UD16CE8
(WH-SDC09C3E8-1) (WH-UD09CE8-1)
(WH-SDC12C9E8-1) (WH-UD12CE8-1)
(WH-SDC14C9E8-1) (WH-UD14CE8-1)
(WH-SDC16C9E8-1) (WH-UD16CE8-1)
ENGLISH
ENGLISH
Before operating the unit, read these operating instructions thoroughly and keep them for future reference.
Before operating the unit, make sure the installation has been carried out correctly by authorized dealer correctly and precisely following the
installation instructions given.
2 ~ 11
2 ~ 11
FRANÇAIS
FRANÇAIS
Avant d’utiliser l’appareil, lisez ce mode d’emploi dans son intégralité et conservez-le pour toute référence ultérieure.
Avant de faire fonctionner l’unité, assurez-vous que l’installation a été correctement réalisée par un revendeur agréé et dans le strict respect des
consignes d’installation fournies.
12 ~ 21
12 ~ 21
ESPAÑOL
Antes de utilizar la unidad, sírvase leer atentamente estas instrucciones de funcionamiento y conservarlas como futuro elemento de consulta.
Antes de operar la unidad asegúrese de que la instalación haya sido realizada correctamente por un instalador autorizado, siguiendo de forma
correcta y precisa las instrucciones de instalación dadas.
22 ~ 31
22 ~ 31
DEUTSCH
Bevor Sie das Gerät in Betrieb nehmen, lesen Sie bitte diese Bedienungsanleitung aufmerksam durch und bewahren Sie
sie für die künftige Verwendung auf.
Vor der Inbetriebnahme dieses Geräts ist sicherzustellen, dass die Montage durch einen autorisierten Händler fachgerecht entsprechend der
Installationsanleitung durchgeführt wurde.
32 ~ 41
32 ~ 41
ITALIANO
Prima di utilizzare l’unità si prega di leggere attentamente le istruzioni e di conservare questo opuscolo per potervi fare riferimento in futuro.
Prima di far funzionare l’unità, assicurarsi che l’installazione sia stata eseguita correttamente da un rivenditore autorizzato e seguendo
precisamente le istruzioni date per l’installazione
42 ~ 51
42 ~ 51
NEDERLANDS
Lees voor u het apparaat gebruikt deze gebruiksaanwijzing grondig en bewaar deze voor toekomstig gebruik.
Controleer, voor u de unit in gebruik neemt, dat de installatie goed is uitgevoerd door een offi ciële dealer en dat dat nauwkeurig is gedaan volgens
de verstrekte instructies voor de installatie.
52 ~ 61
PORTUGUÊS
Antes de ligar a unidade, leia cuidadosamente este manual de utilização e guarde-o para futura referência.
Antes de colocar a unidade em funcionamento, ceritifque-se que a instalação foi feita correctamente por um fornecedor autorizado e que seguiu
com precisão as instruções de instalação dadas.
62 ~ 71
EΛΛΗΝΙΚΆ
Προτού θέσετε τη μονάδα σε λειτουργία, διαβάστε προσεκτικά αυτές τις οδηγίες χρήσης και φυλάξτε τις για μελλοντική αναφορά.
Πριν θέσετε σε λειτουργία τη μονάδα, βεβαιωθείτε ότι η εγκατάσταση έχει διεξαχθεί κανονικά από εξουσιοδοτημένο αντιπρόσωπο, ο οποίος έχει
ακολουθήσει σωστά και πιστά τις δοθείσες οδηγίες
.
72 ~ 81
CZECH
CZECH
Než začnete se zařízením pracovat, důkladně se seznamte s návodem k obsluze a uložte si jej pro pozdější použití.
Než začnete jednotku používat, přesvědčte se, že byla řádně nainstalována podle příslušných pokynů autorizovaným instalačním technikem.
82 ~91
82 ~91
0.2
0.40
0.30.1
MPa
TIMER OUTDOOR
HEAT
COOL
SETTING
DEFROST
STATUS
SERVICE
BOOSTER
QUIET
TANK
WATER OUTLET
C
C
OFF
/
ON
HEATER
OPERATION
FORCE
HEATER
ACTUAL
TIMER
1
MONTUEWEDTHUFRI SATSUN
SOLAR REMOTE
NOT AVAILABLE
2 3 4 56
ON
OFF
©
Panasonic Appliances Air-Conditioning Malaysia
Sdn. Bhd. 2012. Unauthorized copying and distribution
is a violation of law.

Other manuals for Panasonic WH-SDC09C3E8

Questions and Answers

  • A
    Amanda MillerSep 6, 2025
    What causes a Compressor Rotation Failure (F14) in my Panasonic Heat Pump?
    • C
      Crystal HopkinsSep 6, 2025
      A Compressor Rotation Failure (F14) in your Panasonic Heat Pump can be attributed to: * Compressor terminal disconnect. * Faulty outdoor unit PCB (main). * Faulty compressor. The system checks the compressor running condition through the position detection circuit to detect this failure.
  • J
    jonesmichaelAug 22, 2025
    Why is my Panasonic Heat Pump showing Indoor/Outdoor Abnormal Communication (H90)?
    • C
      Colton Barker PhDAug 22, 2025
      An Indoor/Outdoor Abnormal Communication (H90) error on your Panasonic Heat Pump may be due to several reasons: * A faulty outdoor or indoor unit PCB (main). * Indoor-outdoor signal transmission error due to wrong wiring. * A break in the connection wires between the indoor and outdoor units. * A disturbed power supply waveform. The system checks the data received from the outdoor unit during indoor unit signal transmission to ensure it is normal.
  • F
    ffosterSep 4, 2025
    Why is my Panasonic WH-SDC09C3E8 Heat Pump showing Unspecified Voltage between Indoor and Outdoor (H95)?
    • M
      Michael MirandaSep 4, 2025
      An Unspecified Voltage between Indoor and Outdoor (H95) error on your Panasonic Heat Pump may be due to: * Insufficient power supply. * Faulty outdoor unit PCB (noise filter/main). The supply power is detected for its requirement by the indoor/outdoor transmission.
  • D
    David SnyderSep 2, 2025
    What causes an Indoor Freeze-up Protection (H99) error on a Panasonic WH-SDC09C3E8?
    • L
      Leah SmithSep 2, 2025
      An Indoor Freeze-up Protection (H99) error on your Panasonic Heat Pump can occur due to: * A faulty water pump. * Insufficient water flow rate in the system. * Water leak in the system. * A 2 way valve partially closed. * A clogged expansion valve or strainer. * Refrigerant shortage (refrigerant leakage). * A faulty indoor refrigerant liquid temperature sensor. * A faulty indoor unit PCB (main). This protection activates during anti-freezing control in cooling operation when the indoor refrigerant liquid temperature is less than 0°C.
  • S
    Sharon Carr PhDAug 31, 2025
    What does Outdoor High Pressure Protection (H98) mean for a Panasonic WH-SDC09C3E8?
    • A
      Adam BrownSep 1, 2025
      Outdoor High Pressure Protection (H98) in your Panasonic Heat Pump indicates that the pressure is too high. This can be caused by: * A faulty water pump. * Insufficient water flow rate in the system. * Water leak in the system. * 2/3 way closed. * Clogged expansion valve or strainer. * Excessive refrigerant. * Faulty outdoor high pressure sensor. * Faulty outdoor unit PCB (main). During heating operation, this protection is triggered when the outdoor high pressure sensor detects pressure at 4.0MPa and above.
  • A
    Adam ReeseAug 30, 2025
    What causes a Connection Capability Rank Abnormality (H12) in a Panasonic WH-SDC09C3E8?
    • D
      Dr. Jeremy RiveraAug 30, 2025
      A Connection Capability Rank Abnormality (H12) in your Panasonic Heat Pump can be caused by: * Wrong model interconnected. * Wrong indoor unit or outdoor unit PCB (main) used. * Faulty indoor unit or outdoor unit PCB (main). This is determined during the startup operation of cooling and heating, where the capability rank of the indoor unit, checked by the outdoor unit, is used.
  • K
    Katrina ShortAug 29, 2025
    Why is my Panasonic WH-SDC09C3E8 Heat Pump showing an IPM Overheating (F22) error?
    • J
      jorge36Aug 29, 2025
      An IPM Overheating (F22) error on your Panasonic Heat Pump suggests that the IPM (Intelligent Power Module) is overheating. This can be due to: * A faulty outdoor unit fan motor. * A faulty outdoor unit PCB (main). This error is detected during cooling and heating operation when the outdoor IPM temperature sensor detects a temperature of 95°C.
  • J
    Joshua WongAug 27, 2025
    What does Input Over Current Detection (F16) mean on my Panasonic WH-SDC09C3E8?
    • A
      amy17Aug 27, 2025
      Input Over Current Detection (F16) on your Panasonic Heat Pump means that the outdoor current is too high. This can be caused by: * Excessive refrigerant. * Faulty outdoor unit PCB (main). During cooling and heating operation, this error is triggered when the current transformer (CT) in the outdoor unit PCB detects outdoor current above 10.6A.
  • S
    Stephen WilliamsAug 26, 2025
    Why am I getting an Outdoor High Pressure Switch Activate (F12) error on my Panasonic WH-SDC09C3E8 Heat Pump?
    • S
      scotthughesAug 26, 2025
      An Outdoor High Pressure Switch Activate (F12) error on your Panasonic Heat Pump indicates that the outdoor high pressure switch has been activated. This can be due to: * Dust accumulation on the outdoor unit heat exchanger. * Air short circuit at the outdoor unit. * A faulty water pump. * Insufficient water flow rate in the system. * Water leak in the system. * A closed 2/3 way valve. * A clogged expansion valve or strainer. * Excessive refrigerant. * A faulty outdoor high pressure sensor and switch. * A faulty outdoor unit PCB. This occurs during cooling and heating operation when the outdoor high pressure switch detects pressure at 4.5MPa and above.
  • J
    Joseph HoganAug 25, 2025
    What does it mean when my Panasonic WH-SDC09C3E8 displays Outdoor High Pressure Abnormality (H64)?
    • T
      Teresa KingAug 25, 2025
      An Outdoor High Pressure Abnormality (H64) on your Panasonic Heat Pump indicates a problem with the outdoor high pressure sensor. This can be due to: * A faulty connector connection. * A faulty sensor. * A faulty outdoor unit PCB (main). The system detects this abnormality during cooling and heating when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc.

Panasonic WH-SDC09C3E8 Specifications

General IconGeneral
TypeAir-to-Water Heat Pump
Heating Capacity9.00 kW
RefrigerantR32
Energy Efficiency Class HeatingA+++
Energy Efficiency Ratio (Cooling)3.20
Energy Efficiency Ratio (EER)3.20
Operating Temperature Range (Cooling)10°C ~ 43°C

Related product manuals