2
1. Operation and Control
1.1 Auto Mode Operation
1.1.1 Auto Cooling Mode Operation Limit
Auto Mode Cooling Only operation will start once the outdoor ambient temperature reaches 19°C and
compressor will continue to run until the outdoor ambient temperature drops to 16°C.
Due to this limitation,
If Heat to Cool temperature is set lower than 19°C, the compressor will not operates until the outdoor
ambient temperature reaches 19°C or higher.
Outdoor Ambient
16°C
Compressor
ON
Compressor
OFF
19°C
Temperature