Item Unit Indoor Unit
Protection Device A Residual Current Circuit Breaker (30)
Expansion Vessel
Volume I 10
MWP bar 3
Capacity of Integrated Electric Heater / OLP TEMP kW / °C 3.00 / 80
Tank Volume (Spec / Nett) L 200 / 185
Max. Tank Water Set Temperature °C 65
Tank Coil Surface m
2
1.8
Maximum Working
Pressure
Heat / Cool Bar 3.0
Tank Circuit Bar 8.0
Operating Pressure
Tank Unit Bar 3.5
Expansion Relief Valve Bar 8.0
Expansion Vessel Pre-charge Pressure (DHW Circuit) Bar 3.5
Pressure Reducing Valve Set Pressure (DHW Circuit) Bar 3.5
Pressure Vessel
Material En-1.4521
Volume L 185
Design Pressure Bar 10
Heat Exchanger
Material EN-1.4162 / EN-1.4521
Diameter mm 22
Thickness mm 0.8
Surface Area m
2
1.8
Total Length m 25
Note:
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled indoor water inlet
temperature of 12°C and water outlet temperature of 7°C.
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb
(42.8°F Wet Bulb) with controlled indoor water inlet temperature of 30°C and water outlet temperature of 35°C.
Specifications are subjected to change without prior notice for further improvement.
* Above 55°C, only possible with backup heater operation.