4
Item Unit Outdoor Unit
Pipe Diameter
Liquid mm (inch) 6.35 (1/4)
Gas mm (inch) 15.88 (5/8)
Standard Length m (ft) 7 (23.0)
Pipe Length Range m (ft) 3 (9.8) ~ 50 (164.0)
I/D & O/D Height Difference m (ft) 30 (98.4)
Additional Gas Amount g/m (oz/ft) 25 (0.3)
Refrigeration Charge Less m (ft) 10 (32.8)
Compressor
Type Hermetic Motor
Motor Type Brushless (4-poles)
Rated Output kW 1.70
Fan
Type Propeller Fan
Material PP
Motor Type DC (8-poles)
Input Power W
Output Power W 60
Fan Speed rpm
Cooling: 700
Heating: 680
Heat Exchanger
Fin material Aluminium (Pre Coat)
Fin Type Corrugated Fin
Row × Stage × FPI 2 × 30 × 19
Size (W × H × L) mm 38.1 × 762.0 × 865.8 : 895.8
Power Source (Phase, Voltage, Cycle)
Ø Single
V 230
Hz 50
Input Power
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
kW Cooling: 3.02 Heating: 2.01 Heating: 2.06
Maximum Input Power For Heatpump System kW 3.47
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 1Ø / 15.9 / 3.47k
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 1Ø / 13.0 / 3.00k
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) — / — / —
Starting Current A 9.2
Running Current
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
A Cooling: 13.4 Heating: 9.2 Heating: 9.4
Maximum Current For Heatpump System A 15.9
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
% Cooling: 98 Heating: 95 Heating: 95
Power Cord
Number of core -
Length m (ft) -
Thermostat Electronic Control
Protection Device Electronic Control