PLUS 100 AB
Page 28
Rev. 01-08
MANUALE D’USO E MANUTENZIONE
PLUS 100 AB connections diagram
Power section
45-46 Power supply 230 V AC 50 Hz
Inputs section
3-4 Skewer sensor NTC 10K (only cooling)
5-6 Evaporator sensor NTC 10K
7-8 Room sensor NTC 10K
N.B. Terminal 9 is the common of all the digital
inputs
9-14 Pressure lock-out
9-15 Fan overload
9-16 Remote defrost end
9-17 Door switch
9-18 Compressor safety device
Outputs section (no-voltage contacts)
31-32 Freezing solenoid
33-34 Cooling solenoid
35-36 Alarm
37-38 Room light
39-40 Fans
41-42 Defrost
43-44 Compressor
TeleWIN section
19-20 RS485 for TeleWIN
Note:
9-14 and 9-15 stops cold, fans, solenoids. Activates alarm
31-32 Freezing solenoid
(active in freezing process)
33-34 Cooling solenoid (active in cooling process and with compressor during manual function)