TTLAPE03
Pag.14
Rev. 2-09
MAN IN COLD ROOM ALARM KIT COMPONENTS
THE MAN IN COLD ROOM ALARM KIT consists of:
- Visual/acoustic alarm control unit complete with buffer battery.
- N° 3 seals, to be inserted between fixing screw and box backing.
- Emergency cold room light switch.
- Use and maintenance manual.
PRODUCT IDENTIFICATION CODE
TTLAPE03 kit complete with luminous/acoustic man in
cold room emergency alarm.
. TECHNICAL CHARACTERISTICS
Mains power supply 230 V AC 50 Hz
Max consumption on mains power 20 mA
Buffer battery 12 V DC Ni-MH 1300 mAh
Complete recharge time: 110 h
Operating autonomy - With 230 V AC NOT ON
(running on charged buffer battery) : 14 h approx.
- With 230 V AC power ON: unlimited
Out-of-room module IP 43 protection rating
Operating temperature: -5 - +45 °C
Acoustic characteristics
Type: piezoelectric
Sound power: 90 dB at 1m
Visual warning Flashing red LED, 12 V DC
In-room emergency pushbutton Lighting: red LED, 12 V DC
NC contact
Keypad with IP65 protection rating
Operating temperature: -25 - +70 °C
Auxiliary relay 8A AC1 (contact closes with alarm on)
- ENG -
USE AND MAINTENANCE MANUAL
CHAPTER 1: INTRODUCTION
CHAP. 1 - Introduction