E507S-2LS-2
DOUBLE-POLE LINE-SENSING THERMOSTAT FOR HAZARDOUS LOCATIONS
INSTALLATION INSTRUCTIONS
THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceE507S2LS2-IM-H5691401/13
DESCRIPTION
The E507S-2LS-2 thermostat is designed for controlling heat-
tracing systems in hazardous locations. The thermostat functions
as a DPST switch. The DPST switch will enable and disable current
flow in both buses of the heat-tracing cable.
The E507S-2LS-2 can be used to control heat-tracing circuits in a
pipe-sensing mode (see Figure 1 on back page).
Note: Do not use this thermostat to control two separate heat-
tracing circuits.
ADDITIONAL MATERIAL REQUIRED
ǩAT-180 aluminum tape
APPROVALS
SPECIFICATIONS
Enclosure NEMA 4, 7, 9, lacquer-coated cast-aluminum
housing, stainless-steel hardware
Entries One 3/4 in. NPT conduit hub
Set point range 25°F to 325°F (–4°C to 163°C)
Sensor exposure
limits
–40°F to 420°F (–40°C to 215°C)
Housing exposure
limits
–40°F to 140°F (–40°C to 60°C)
Switch DPST
Electrical rating 22 A at 208/240 Vac
Relay coil 208–240 Vac, 4 VA
Accuracy ±6°F (±3.3°C)
Deadband 2°F to 12°F (1.1°C to 6.7°C) above actuation
temperature
Set point
repeatability
±3°F (±1.7°C)
Sensor type Fluid-filled (silicone) bulb and 9 ft (2.7 m)
capillary
Sensor material 300 series stainless steel
Connection
terminals
Screw terminals, 10–14 AWG (2–5 mm
2
)
Class I, Div. 1 and 2, Groups B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III
Hazardous locations
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
installation instructions.
Component approvals and performance are based on the use of
specified parts only. Do not use substitute parts or vinyl electrical
tape to make connections.
WARNING:
4.0 in (102 mm)
8.0 in
approx.
4.5 in (114 mm)
Ø.28 in (7 mm)
mounting hole
(4X)
4.5 in
(114 mm)
6.6 in
(168 mm)
4.0 in
(102 mm)
Adjusting
knob
Removable
knob cover
1.2 in
(30 mm)
3⁄4 in NPT conduit entry
2.0 in
(50 mm)
6.0 in (153 mm)
Terminal
block
Question and Answer IconNeed help?

Do you have a question about the Pentair Digitrace E507S-2LS-2 and is the answer not in the manual?

Pentair Digitrace E507S-2LS-2 Specifications

General IconGeneral
BrandPentair
ModelDigitrace E507S-2LS-2
CategoryThermostat
LanguageEnglish

Summary

Product Description and Approvals

Product Description

Thermostat for controlling heat-tracing systems in hazardous locations, functions as a DPST switch.

Additional Material Required

Lists required AT-180 aluminum tape for installation.

Hazardous Location Approvals

Lists UL, FM, and SP hazardous location approvals for Class I, II, and III.

Technical Specifications

Enclosure and Entries

Details NEMA 4, 7, 9 enclosure type and one 3/4 in. NPT conduit hub entry.

Temperature and Limits

Specifies set point range and sensor/housing exposure limits.

Electrical Ratings and Performance

Covers electrical rating, relay coil, accuracy, deadband, and repeatability.

Sensor and Connection Details

Describes sensor type, material, and connection terminals.

Installation and Setup

Installing the Thermostat

Instructions for verifying suitability, checking ratings, and mounting the unit.

Positioning the Sensor Bulb

Guidance on placing the sensor bulb on the pipe for accurate sensing.

Setting the Thermostat

Steps for setting the temperature dial and completing insulation.

Wiring Diagram

Heat-Tracing Control Wiring

Diagram illustrating the wiring connections for heat-tracing control.