M52 DESIGN DATA
Model Availability Voltage Hz
Full Load
Amps
Phase
BTU/Hr. @
Max Ambient
Temperature
Max Ambient
Temperature
(°F/°C)
Shipping
Weight
(lb./kg)
M28-0626-GXXX 115 50/60 13.0/13.0 1 5000/6000 125/52 155/70
M52-0626-XXX 230 50/60 6.5/6.5 1 5000/6000 125/52 155/70
M52-0816-032 Stock 115 50/60 14.5/14.5 1 6700/8000 125/52 160/73
M52-0816-XXX 115 50/60 14.5/14.5 1 6700/8000 125/52 160/73
M52-0826-015 Stock 230 50/60 8.0/8.0 1 6700/8000 125/52 160/73
M52-0826-XXX 230 50/60 8.0/8.0 1 6700/8000 125/52 160/73
M52-1016-038 Stock 110/115 50/60 18.9/19.5 1 8300/10000 125/52 165/75
M52-1016-XXX 110/115 50/60 18.9/19.5 1 8300/10000 125/52 165/75
M52-1026-021 Stock 220/230 50/60 9.5/9.8 1 8300/10000 125/52 165/75
M52-1026-XXX 220/230 50/60 9.5/9.8 1 8300/10000 125/52 165/75
M52-1216-017 Stock 110/115 50/60 24.0/23.0 1 10000/12000* 125/52 175/79
M52-1216-XXX 110/115 50/60 24.0/23.0 1 10000/12000* 125/52 175/79
M52-1226-034 Stock 220/230 50/60 12.2/11.6 1 10000/12000* 125/52 175/79
M52-1226-XXX 220/230 50/60 12.2/11.6 1 10000/12000* 125/52 175/79
-XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specific model numbers.
* Based on return air temperature slightly above ambient.