12000 BTU/HR. UNIT CHARACTERISTICS
Part Number
G521216GXXX G521226GXXX G521246GXXX
Dimensional Data
Height 52.69/1338.4 mm
Width 17.12/435 mm
Depth 11.66/296.1 mm
Unit Weight 131 lbs/59.4 kg 141 lbs / 64.0 kg
Unit Protection Rating Type 12/4/4X/3R
Cooling Data
Refrigerant R134A
Refrigerant Charge 38 oz.
Cooling Capacity at 95 F Enclosure 95 F
Ambient (BTU/Hr./W)
9900/10700
Cooling Capacity at Max Conditions
(BTU/Hr./W)
12000/12500 11000/12000
Maximum Ambient Temp 131 F/55 C
Minimum Ambient Temp -40 F/-40 C
Enclosure Airflow 287/305 CFM
External Airflow 635/650 CFM
Condensate Management Hose discharge/Optional powered C/E
Heating Data
Capacity 2000W N/A
Electrical Data
Rated Voltage (50/60 Hz) 115V 230/208-230V 400/460V 3 phase
Rated Frequency 50/60 Hz
Voltage Range +/- 10% of rated
Cooling Amps at Max Conditions 16.1/21.0 9.1/10.6 - 9.5 3.5/3.7
Heating Amps 17.3 9.6 N/A
Compressor RLA / LRA 9.8/57.0 4.9/38.0 2.1/16/0
Evaporator Fan RLA* .5 .3 .4
Condenser Fan RLA* .5 .3 .4