© 2015 Pentair Equipment Protection
89104464
- 4 -
INSTALLATION INSTRUCTIONS
1. Inspect the air conditioner and verify correct functionality before mounting the air conditioner. See
HANDLING AND TESTING THE AIR CONDITIONER on page 3.
2. Using the cutout dimensions shown in this manual, prepare the air “IN” and air “OUT” openings,
and mounting bolt hole pattern for the enclosure.
3. Using the gasket kit provided, install gaskets to air conditioner. See Mounting Gasket Kit on page
7 of this manual for proper location.
4. Mount air conditioner on enclosure using mounting bolts and screws provided. “EZ” mount tabs
can be used to hold unit on enclosure while mounting in place. Allow unit to remain upright for a
minimum of five (5) minutes before starting. Caution! Air conditioner must be in upright position
during operation.
5. When routing the drain tube, caution should be taken to keep it from kinking or being elevated
above the exit point of the air conditioner. The drain tube must be on a continuous downward
slope. A slight elevation of the tube could result in secondary trap. FAILURE TO FOLLOW THESE
COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN.
6. Refer to top of nameplate for electrical requirements. Connect the power cord to a properly
grounded power supply. Use of an extension cord is not recommended. Electrical circuit should be
fused with slow blow or HACR circuit breaker.
TECHNICAL INFORMATION
DESIGN DATA
Model Voltage Hz
Full Load
Amps
Phase
BTU/Hr @
Max Amb
Max Amb
Temp
°F/°C
Shipping
Weight
lb./kg
T290416GXXX 115 50/60 13.0/12.8 1 3600/4000 131/55 107/48.6
T290426GXXX 230 50/60 4.7/4.9 1 3600/4000 131/55 107/48.6
-XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specific model numbers.