EasyManua.ls Logo

Pepperl+Fuchs KCD2-SR-1.LB - Page 15

Pepperl+Fuchs KCD2-SR-1.LB
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Proof Test
2014-09
15
Figure 4.3 Proof test set-up for HiC2821, HiC2822
Channel 2 only for HiC2822.
HiC2822
Termination Board
Zone 0, 1, 2
Div. 1, 2
Zone 2
Div. 2
11
14
12
15
1+
4-
2+
5-
Multimeter
(mA)
Multimeter
(mA)
Multimeter
( mA )
R
LB
R
SC
Multimeter
( mA )
R
LB
R
SC
240 R / 2.5 W
24 V DC
Multimeter
( mA )
240 R / 2.5 W
24 V DC
Supply +
Supply -
24 V DC
Power
supply
I supply
Supply
Bus
Tip
Normally the easiest way to test H-System modules is by using a stand-alone
HiCTB08-UNI-SC-SC Termination Board. The tester then has no need to
disconnect wires in the existing application, so subsequent miswiring of the
module is prevented.