Safety Manual SIL KFD2-ST*4-(Ex)*, KFD2-CR4-(Ex)*
Planning
2014-09
11
KFD2-CR4-(Ex)1.2O, KFD2-STC4-(Ex)1.2O, KFD2-STC4-(Ex)1.2O-3,
KFD2-STC4-(Ex)1.2O-Y*, KFD2-STV4-(Ex)1.2O-1, KFD2-STV4-(Ex)1.2O-2
Parameters acc. to IEC 61508 Values
Assessment type FMEDA report
Device type A
Demand mode Low Demand Mode or High Demand Mode
Safety function
2
Transfer of analog values
HFT 0
SIL 2 3
Input and output function Input Output Single output
used in safety
function
Both outputs used
in safety function
s
120 FIT 144 FIT 264 FIT 670.2 FIT
dd
1
71.6 FIT 95.3 FIT 166.9 FIT 85.4 FIT
du
14.4 FIT 43.8 FIT 57.2 FIT 16.6 FIT
no effect
2
120 FIT 144.1 FIT 264 FIT 408 FIT
not part
107 FIT 205 FIT 312 FIT 517 FIT
total (safety function)
206 FIT 284 FIT 490 FIT 774 FIT
SFF 88 % 97 %
MTBF
3
142 years 147 years
PFH
4
5.72 x 10
-8
1/h 1.66 x 10
-8
1/h
PFD
avg
for T
proof
= 1 year 2.50 x 10
-4
7.26 x 10
-5
PFD
avg
for T
proof
= 2 years 5.01 x 10
-4
1.45 x 10
-4
PFD
avg
for T
proof
= 5 years 1.25 x 10
-3
3.63 x 10
-4
1
"Fail high" and "Fail low" failures are considered as dangerous detected failures
dd
.
2
"No effect" failures are not influencing the safety functions and are therefore added to the
s
.
3
acc. to SN29500. This value includes failures which are not part of the safety function.
4
The safety characteristic values were calculated considering a common cause factor of 5 % for the safety
relevant output part. For the application with both outputs in the safety function, the ESD system needs to
evaluate if the outputs differ by more than 2 %.
Table 2.3