EasyManua.ls Logo

Pfannenberg DTI 6801 - Equipotential Bonding and Fuses

Pfannenberg DTI 6801
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENG
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) 400 / 460 V, 3~ | 086100125 45/66
4.6.9 Equipotential bonding connections and fuses
1 Functional equipotential bonding (M8-thread), for a
signal reception with low interference between the unit
and the switch cabinet.
2 Fuses (F2, F3) for transformer as protection against
fault current, overload current and short-circuit current.
Fig. 21: Equipotential bonding/fuses
Replacement of fuses
I
n order to maintain the UL-conformity, only spare fuses with the following specification may be used:
Control fuse
Version: Category Class CC”, slow-blow, suitable for transformer protection, voltage strength at least 480 V
DTI / DTS 6801 Maximum 3.0 A
Tab. 12: Fuse specification
NOTE
Potential equalization provided by customer
If the device is to be integrated into the customer’s existing potential equalization for EMC reasons, a conductor can be
connected at the connecting point of the function potential equalization.
The connecting point is labeled with the necessary circuit symbol.
G00014-01