Pfannenberg PWS 7 Series - User Manual

Pfannenberg PWS 7 Series
39 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Stand 09.97
Betriebs- und Montageanleitung
Operating- and installation
instructions
Notice de montage et d'utilisation
PWD 5302
PWD 5402
PWS 7 . . .

Table of Contents

Questions and Answers

  • A
    Albert FloresAug 11, 2025
    Why is my Pfannenberg Industrial Equipment unit not cooling sufficiently?
    • S
      samuel80Aug 11, 2025
      Your Pfannenberg Industrial Equipment might not be cooling well due to several reasons: the fan may not be turning correctly (check the voltage or replace the fan), the cooling water might be too hot or the volume might be too low (check the cooling water supply). Also, the louvres on the heat exchanger might be dirty (clean with a brush or compressed air), the cooling water could be dirty (use only clean cooling water), or there might be additives in the cooling water, such as glycol, which can reduce cooling performance.
  • K
    Kristopher JohnsonAug 18, 2025
    What to do if my Pfannenberg Industrial Equipment unit cools at all times?
    • A
      Allen ThompsonAug 18, 2025
      If your Pfannenberg Industrial Equipment unit is constantly cooling, it could be because the solenoid valve coil is dirty and remains open (clean the valve). Another possibility is that the supply and return lines are confused (check the connections and direction of flow).
  • K
    Kimberly PenaAug 26, 2025
    What to do if my Pfannenberg Industrial Equipment unit with solenoid valve fails to cool or cools insufficiently?
    • K
      Keith GrayAug 26, 2025
      If your Pfannenberg Industrial Equipment unit with a solenoid valve isn't cooling properly, first check the thermostat setting. If that's not the issue, the solenoid valve coil might be defective (replace the coil) or clogged (clean the valve).
  • L
    Laura SampsonSep 2, 2025
    What to do if my Pfannenberg Industrial Equipment unit with water-capacity controller fails to cool or cools insufficiently?
    • A
      Alison BooneSep 2, 2025
      If your Pfannenberg Industrial Equipment unit with a water-capacity controller is not cooling well, check the thermostat setting first. If the setting is correct, the thermostat head might be defective (replace it) or the control valve could be clogged (clean the control valve).

Pfannenberg PWS 7 Series Specifications