DDNG485 Installation Instructions Rev 10 Specications subject to change without notice
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-Mail: support.controls@philips.com Web: http://philips.com/dynalite
Input Voltage: 12 VDC max, 375 mA from the DyNet network (port 1)
RS485 Serial Port 1: 1 x RS485 unterminated, consisting of 1 x 6 way terminal block
RS485 Serial Port 2: 1 x RS485 unterminated, consisting of 1 x RJ12 socket & 1 x 5 way terminal block
Serial Port Isolation: Opto Isolated to 3.75 KV
RS485 Data Formats: DyNet, DyNet II, DMX512 Receive 64 channels
Supported Baud rates: 1200 - 460800
Output Terminals: 12 x DALI, 0-10V, DSI driver circuits: DA+, DA-
conductor size 0.2 - 5mm
2
(24 - 10 AWG)
User Controls: Service switch, Diagnostic LED
Internal Controls: Programmable Logic Controller, 64 tasks
Operating Conditions: Temperature: 0 to 50° C ambient
Humidity: 0 to 90% non-condensing
Storage & Transport: Temperature: -25 to 60° C ambient
Humidity: 0 to 90% non-condensing
Construction: Polycarbonate DIN rail enclosure
Dimensions: 95 mm x 105 mm x 75 mm (3.8” x 4.1” x 2.9”)
Packed Weight: 0.25 kg
Certication: CE, RCM
Recommended Cable Type
Dynalite DYNET-STP-CABLE or equivalent shielded
three twisted-pair.
See datasheet for more information.
Recommended Cable Color Coding
Green/White Pair Paralleled for GND
Orange/White Pair Paralleled for +12VDC
Blue/White Pair Blue for DATA+
White for DATA-
Brown/White Pair Spare, use for SHIELD on unshielded cables
SHLD
GND
D+
D-
+12V
Aux
Shield
Green/Green white
Blue
Blue white
Orange/Orange white
Brown/Brown white
+VE
+VE
D –
D +
GND
GND
RS485 DyNet network
Product Specications
Example of trunk and spur topology
Sensor
DUS360CR
DyNet Trunk
DyNet Spur
To up to 59 more devices
DDNG485
Network Gateway
DyNet Trunk
DyNet Spur
To up to 59 more devices
To other
floors
To other
floors