8 Product Guide - LRM1070, LRM1080
Specications
Mains connection
Voltage 230V
AC
+/10%; 50/60Hz
Maximum load 6 A. (1380 VA) any load
Connector screw
terminal
MRT3P7.62-3VE or
GMVSTBW2.5/3-ST-7.62
Maximum wire range 1.5 to 2.5mm
2
Mains distribution
system
TN-S, 16A max, with
Neutral grounded
Power consumption
Stand-by 1.2 W
Max. 1.2 W
Environmental
Temperature +5 to +50°C (operating)
-20 to +7C (storage and
transport)
Relative humidity 20% to 90% (no
condensation)
Parallel interface
Maximum 10 units in parallel
SELV signal, max 5 V.
Free Topology Wiring
Polarity sensitive
Connector type screw terminal
CPF5.08-2VE or
MSTB2.5/2-ST-5.08
Maximum wire range 1.5 to 2.5mm
2
Maximum length 100m
Settings
LED indicator Red on movement
detection
Switch o delay 1 to 30 minutes
Light levels 250 to 1000 Lux
(30% reection)
Detection range see diagram
The remote control and
light sensor work in a
similar range.
Compliances and approvals
Standards EN/IEC 60669-2-1
Electronic switches
Classication Class I
Pollution degree 2
Over voltage category III
Approbation Product complies with
the relevant European
Directive (CE)
KEMA
EMC
Compliance IEC (EN) 60669-2-1
Immunity IEC (EN) 61547
Emission IEC (EN) 55015 and IEC
(EN) 55022, class B
Housing
Protection Class IP20
Flammability UL94 V-0
Glow wire test 960°C/5s.
Insulation Double
insulation
(4kV) between Mains
and SELV
Weight 0.2 Kg

Related product manuals