PICK VARIABLE FLOW SERVICE MANUAL
9
Steam quality may be poor
(excess condensate
entrained in steam
-Examine the steam
system, correcting any
deficiencies
-Install a drip leg with
steam trap, upstream of
the strainer, to maintain
high quality steam at
the heater
See
installation
manual
Steam control valve
positioned less than 20%
open (operating below
minimum turndown)
Check steam valve
travel when operating.
Valve must be open
more than 20% open.
Consult Pick Heaters
about a smaller or dual
steam valve
arrangement
21
Steam control valve moves
too fast (only with non-
standard or faulty
temperature controller)
The temperature
controller should be
tuned to allow 7-10
seconds for full valve
travel
Injection tube problem Refer to detailed
instructions for
disassembly and
inspection of the heater
and injection tube.
Replace piston, spring
or injection tube if
required
11-13
Crack or hole in steam flow Repair or replace inlet
house.
CONSULT FACTORY
Steam control valve moves
too fast due to use of valve
positioner(s)
Remove valve
positioner(s)
Steam valve opening
pressure out of adjustment
Adjust valve according
to steam valve
instruction manual
20
Valve packing gland too
tight
Adjust packing gland
according to valve
manual
21
Unstable steam pressure
reducing valve upstream of
the system
Examine reducing
valve, repair or replace
if necessary