EasyManua.ls Logo

Potter PAD100-PSSA - User Manual

Default Icon
3 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Installation Manual: PAD100-PSSA/PSDA Pull Station (Single & Dual Action)
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the PAD100-PSSA / PSDA (Single Action / Dual Action)
module. This module is only compatible with addressable re systems that utilize the PAD Addressable Protocol.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National
Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For
further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system
operation.
1. Description
The PAD100-PSSA (Single Action) is activated by pulling the white "T" bar handle down. The PAD100-PSDA (Dual Action) is
activated by lifting the front cover and then pulling the white "T" bar handle down. Once activated, the "T" bar cannot be reset
without opening the front cover. Opening the front cover will also activate the pull station. To reset the PAD100-PS series, use the
Potter WS-93 key to unlock and open the front cover. Once the cover is open, push the "T" bar back into the normal position and
re-secure the front cover. It is a non-coded addressable pull station and installs on a single gang box or surface mounts using the
P32-BB or P32-DBB (deep) back box.
2. Setting the Address
All PAD protocol detectors and modules require an address prior to connection to the panel's SLC loop. Each PAD device's
address (i.e., detector and/or module) is set by changing the dip switches located on the device. PAD device addresses are
comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127.
Figure 1. PAD Device Dip Switch Addresses Table (Addresses 1127)
Note: Each "gray" box indicates that the dip switch is "On," and each "white" box indicates "Off."
The examples shown below illustrate a PAD device's dip switch settings: the 1st example shows a device not addressed where all
dip switch settings are in the default "Off" position, the 2nd illustrates an addressed PAD device via the dip switch settings.
Figure 2. Examples of PAD Device Showing Default Dip Switch Setting (Unaddressed) & Addressed PAD Device
Document 5406320-A 02/16
Potter Electric Signal Co., LLC St. Louis, MO Phone: (866) 956-0988 www.pottersignal.com
PAGE 1 OF 3
1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64
1 27 53 78 103
2 28 54 79 104
3 29 55 80 105
4 30 56 81 106
5 31 57 82 107
6 32 58 83 108
7 33 59 84 109
8 34 60 85 110
9 35 61 86 111
10 36 62 87 112
11 37 63 88 113
12 38 64 89 114
13 39 65 90 115
14 40 66 91 116
15 41 67 92 117
16 42 68 93 118
17 43 69 94 119
18 44 70 95 120
19 45 71 96 121
20 46 72 97 122
21 47 73 98 123
22 48 74 99 124
23 49 75 100 125
24 50 76 101 126
25 51 77 102 127
26 52 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64
1 2 4 8 16 32 64 1 2 4 8 16 32 64
Off
On
1 2 4 16
8 32 64
All dip switches are
shown in the "Off"
position.
Off
On
1 2 4 16
8
32 64
Example shows this PAD device's
address = 42. Dip switches #2, 8 &
32 are in the "On" position.
Question and Answer IconNeed help?

Do you have a question about the Potter PAD100-PSSA and is the answer not in the manual?

Potter PAD100-PSSA Specifications

General IconGeneral
BrandPotter
ModelPAD100-PSSA
CategoryFire Alarms
LanguageEnglish