Pre Charge (3)
Identifies the battery voltage before charging.
If the battery voltage is lower than the reference voltage, the
battery will be pre-charged in order to avoid damage to the
battery.
12V: 5-8V 2 minutes, 8-10V 9 hours.
24V: 5-16V 2 minutes, 16-20V 9 hours.
Constant Current (4)
The main charging phase.
The battery will be charged with the maximum current as
quickly as possible.
70%~85% of the battery is charged in this stage.
Constant Voltage (5)
The boosting phase.
The charger constantly adjusts the charge so as the battery
voltage gets higher, the charging current becomes smaller.
Constant voltage charging ends when the charging current
drops to =< 0.5C, at which time the battery should be almost
fully charged.
Recondition (6)
When the battery has reached maximum voltage, the charge
changes to recondition mode since some batteries can be
charged to 15.7V.
This charge lasts 2±0.2 hours at most and is only activated by
selecting 12V/RECON.
Voltage Analysis (7)
The internal circuit automatically detects the variation of
battery voltage.
An alarm will sound when the voltage exceeds 2V (12V) or 4V
(24V).