18 4801 V100-UK
TYPE 4801 ................................................................. Modbus Gateway
Applications................................................................ PPS application communications
gateway and Modbus RTU to
Ethernet Modbus TCP/IP gateway.
Specifications:
Supply voltage .......................................................... 12...48 VDC - 4.5 W - max. 340 mA
Operating temperature .......................................... -10...+60 °C
LAN1, RJ45 ................................................................. PPS communication port
”device s/n”.pps.prelectronics.com
- IP: Dynamic
LAN2, RJ45 ................................................................. Modbus TCP/IP - IP: 169.254.0.10 -
Subnet mask: 255.255.0.0
Port 1 and 2, DB9 male ......................................... Modbus RTU over RS - 485
(default baud rate: 57.6k bps)
Upto 32 PR 4511 devices can be
connected directly to each Port.
Accessories................................................................. 2 pcs. of SUB-D9 to RJ45 cables are
included (200 mm) - for conneting
the 4511 devices to the Modbus
RTU P1 and P2 ports.
4801 gateway specifications