16 2231V104-UK
1.3 InC / dEC - Setting of active relay 1 for increasing / decreasing
input signal
Possible selections are InC or dEC.
If InC is selected, relay 1 will be activated when the input value is high er
than the setpoint and deactivated again, when the input value is lower
than the setpoint minus the hysteresis. If dEC is selected, relay 1 will
be activated when the input value is lower than the setpoint and be
deactivated again when the input value is higher than the setpoint plus
the hysteresis.
When the selected function in menu 4.1 = {004 = Setpoint window},
InC will result in the activation of the relay, and dEC will result in the
deactivation of the relay inside the window.
1.4 dEL - Setting of relay 1 time delay
Possible selections are 0...99.9 s.
The time delay is the period in which the input value must be present
before the relay switches state.
1.5 HyS - Setting of hysteresis for setpoint window
Possible selections are 0...99.9%.
When the selected function in menu 4.1 = {004 = Setpoint window},
menu 1.5 is active. The hysteresis is set in % of the input signal and is
placed outside the window.
A hysteresis less than 1% is typically an acceptable value.
2.0 rE2 - SETTING OF PARAMETERS FOR RELAY 2
When the selected function in menu 4.1 = {001 = Single setpoint}, all sub-
menus (2.1 to 2.5) have no function.
2.1 SEt / SPL - Setting of relay 2 setpoint
Possible selections are 0...99.9%.
The setpoint is set in % of the input signal.
When the selected function in menu 4.1 = {003 = Pre-setpoint}, the
percentage pre-setpoint value in relation to the relay 2 setpoint is set.
Menus 2.3 to 2.5 have no function.When the selected function in menu 4.1
= {004 = Setpoint window}, the low window value SPL is set in this menu.
When the selected function in menu 4.1 = {005 = Hold}, the value that
activates the hold function on relay 2 is set.